OBC DIVISION B · PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Section 9.20 — Masonry and Insulating Concrete Form
Full text of Section 9.20 (Masonry and Insulating Concrete Form) — Division B, Part 9 (Housing and Small Buildings) of the 2024 Ontario Building Code, with every article reproduced below.
9.20.1.Application
(1) Except as provided in Article 9.20.1.2., this Section applies to
(a) unreinforced masonry and masonry veneer walls not in contact with the ground, where
(i) the height of the walls constructed on the foundation walls does not exceed 11 m, and
(ii) the roof or floor assembly above the first storey is not of concrete construction, and
(b) flat insulating concrete form walls not in contact with the ground that (See Note A-9.15.1.1.(1)(c) and
9.20.1.1.(1)(b))
(i) have a maximum floor-to-floor height of 3 m,
(ii) are erected in buildings not more than 2 storeys in building height, and
(iii) are erected in locations where the seismic spectral response acceleration, S a(0.2), is not greater than 0.4.
(See Note A-9.20.1.2.)
(2) For walls other than those described in Sentence (1), or where the masonry walls or insulating concrete form walls
not in contact with the ground are designed for specified loads on the basis of ultimate and serviceability limit states,
Subsection 4.3.2. shall apply.
9.20.1.2.Earthquake Reinforcement (See Note A-9-20.1.2.) permalink →
(1) In locations where the seismic spectral acceleration, Sa(0.2), is greater than 0.55, loadbearing elements of masonry
buildings more than 1 storey in building height shall be reinforced with not less than the minimum amount of
reinforcement as required by Subsection 9.20.15.
(2) In locations where the seismic spectral acceleration, Sa(0.2), is greater than 0.35, but less than or equal to 0.55,
loadbearing elements of masonry buildings 3 storeys in building height shall be reinforced with not less than the
minimum amount of reinforcement as required by Subsection 9.20.15.
9.20.2.Masonry Units
9.20.2.1.Masonry Unit Standards permalink →
(1) Masonry units shall comply with
(a) ASTM C73, “Standard Specification for Calcium Silicate Brick (Sand-Lime Brick),”
(b) ASTM C126, “Ceramic Glazed Structural Clay Facing Tile, Facing Brick, and Solid Masonry Units,”
(c) ASTM C212, “Standard Specification for Structural Clay Facing Tile,”
(d) CAN/CSA-A82 “Fire masonry brick made from clay or shale,”
(e) CSA A165.1, “Concrete block masonry units,”
(f) CSA A165.2, “Concrete brick masonry units,” or
(g) CSA A165.3, “Prefaced concrete masonry units.”
(1) Used bricks shall be free of old mortar, soot or other surface coating and shall conform to Article 9.20.2.1.
(1) Glass blocks shall not be used as loadbearing units or in the construction of fireplaces or chimneys.
9.20.2.4.Cellular Concrete permalink →
(1) Masonry made with cellular concrete shall not be used in contact with the soil or exposed to the weather.
(1) Stone shall be sound and durable.
9.20.2.6.Concrete Units Exposed to the Weather permalink →
(1) Concrete blocks exposed to the weather shall have density and water absorption characteristics conforming to
concrete types A, B, C, or D described in CSA A165.1, “Concrete block masonry units.”
9.20.2.7.Compressive Strength permalink →
(1) The compressive strength of concrete blocks shall conform to Table 9.20.2.7.
Table 9.20.2.7.
Compressive Strength of Concrete Blocks
Forming Part of Sentence 9.20.2.7.(1)
Minimum Compressive Strength Over Net Area, MPa
Type of Unit
Exposed to Weather Not Exposed to Weather
Solid or hollow concrete blocks 15 10
Solid loadbearing cellular blocks Not permitted 5
Solid non-loadbearing cellular blocks Not permitted 2
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.20.3.Mortar
9.20.3.1.Mortar Materials permalink →
(1) Cementitious materials and aggregates for mortar and grout shall comply with CAN/CSA-A179, “Mortar and grout
for unit masonry.”
(2) Water and aggregate shall be clean and free of significant amounts of deleterious materials.
(3) Lime used in mortar shall be hydrated.
(4) If lime putty is used in mortar, it shall be made by slaking quicklime in water for not less than 24 h or soaking
hydrated lime in water for not less than 12 h.
9.20.3.2.Mortar and Grout Mixes permalink →
(1) Mortar types shall be in accordance with Table 9.20.3.2.-A.
(2) Mortar for glass block masonry shall be
(a) Type S Portland cement-lime where exposed to the exterior, or
(b) Type S or N where protected from the exterior.
(3) Mortar shall be mixed within the proportion limits provided in Table 9.20.3.2.-B, with sufficient water to bring the
mixture to a consistency adequate for laying masonry units.
(4) Grout shall be mixed within the proportion limits provided in Table 9.20.3.2.-C, with sufficient water to provide a
suitable flow to fill all voids completely, without excessive segregation or bleeding.
(5) Except as provided in Sentence (6), mortar shall be used and placed in final position
(a) within 1.5 h after mixing when the air temperature is 25°C or higher, or
(b) within 2.5 h after mixing when the air temperature is less than 25°C.
(6) Mortar and grout containing a set-control admixture shall be manufactured off-site in a batching plant and shall be
used and placed in final position within a time not exceeding the useful life stipulated by the manufacturer.
(7) Grout used for reinforced masonry shall be placed in accordance with the requirements of CAN/CSA-A371,
“Masonry construction for buildings.”
Table 9.20.3.2.-A
Mortar Use
Forming Part of Sentence 9.20.3.2.(1)
Location Building Element Mortar Type
Loadbearing walls and columns S
Exterior, Above Ground Non-loadbearing walls and columns N or S
Parapets, chimneys and masonry veneer N or S
Exterior, At or Below Ground Foundation walls and chimneys S
Loadbearing walls and columns N
Interior
Non-loadbearing walls and columns N
Table 9.20.3.2.-B
Mortar Mix Proportions (by Volume)
Forming Part of Sentence 9.20.3.2.(3)
Mortar Fine Aggregate
Portland Cement Lime Masonry Cement Type N Masonry Cement Type S
Type (damp, loose-state sand)
1 ½ — — 3½ to 4½
S — — — 1 2¼ to 3
½ — 1 — 3½ to 4½
1 1 — — 4½ to 6
N
— — 1 — 2¼ to 3
Table 9.20.3.2.-C
Grout Mix Proportions (by Volume)
Forming Part of Sentence 9.20.3.2.(4)
Portland Cement Lime Fine Aggregate (sand) Coarse Aggregate
2¼ to 3 times the sum of the 1 to 2 times the sum of the cement
1 0 to 1/10
cement and lime volumes and lime volumes
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.20.4.Mortar Joints
(1) Except as provided in Sentence (2), mortar joint thickness for burned clay brick and concrete masonry units shall be
10 mm.
(2) Permitted tolerances in head and bed joints shall be not more than -5 mm to +10 mm.
9.20.4.2.Masonry Units permalink →
(1) Hollow masonry units shall be laid with mortar applied to head and bed joints of both inner and outer face shells.
(2) Vertically aligned webs of hollow masonry units shall be laid in a full bed of mortar
(a) under the starting course,
(b) in all courses of columns, and
(c) where adjacent to cells or cavities that are to be filled with grout.
(3) Except for head joints left open for weep holes and ventilation, solid masonry units shall be laid with full head and
bed joints.
9.20.5.Masonry Support
9.20.5.1.Masonry Support permalink →
(1) All masonry shall be supported on masonry, concrete or steel, except that masonry veneer walls may be supported
on foundations of wood frame constructed in conformance with Sentence 9.15.2.4.(1). (See Note A-9.20.5.1.(1))
(2) Every masonry wall shall be at least as thick as the wall it supports, except as otherwise permitted in
Article 9.20.12.2.
9.20.5.2.Lintels or Arches permalink →
(1) Masonry over openings shall be supported by steel, reinforced concrete lintels or masonry arches designed to
support the imposed loads.
(2) Except as provided in Sentences (3) and (5), steel angle lintels supporting masonry above openings shall conform to
Table 9.20.5.2.-A.
(3) Steel angle lintels supporting masonry veneer above openings shall conform to Table 9.20.5.2.-B.
Table 9.20.5.2.-A
Loose Steel Lintels for Masonry – No. & Size of Angles Required(1)(2)
Forming Part of Sentence 9.20.5.2.(2)
Exterior Angles, mm Interior Angles, mm
For Brick For Stone
Wall Maximum Floor Loads per Metre of Span in Newtons(4)(6)(7)
Clear
100 mm + 50 mm Thickness,
Span(3)(5) 100 mm
stone facing mm
None 3 650 7 300 10 950 14 600 18 250 21 900
No Floor Load
L-89 L-89 L-89 L-102 L-127 L-127 L-127
203 × 89 × 89 × 89 × 89 × 89 × 89 × 89
1.2 m or × 6.4 × 6.4 × 7.9 × 7.9 × 7.9 × 11 × 13
L-89 × 89 × 6.4 L-127 × 89 × 7.9
less 2Ls-89 2Ls-89 2Ls-89 2Ls-89 2Ls-89 2Ls-102 2Ls-102
305 × 89 × 89 × 89 × 89 × 89 × 89 × 89
× 7.9 × 7.9 × 7.9 × 7.9 × 7.9 × 7.9 × 7.9
L-89 L-89 L-127 L-127 L-127 L-152
203 × 89 × 89 × 89 × 89 × 89 × 89
× 7.9 × 7.9 × 7.9 × 11 × 13 × 11
1.5 m L-89 × 89 × 7.9 L-127 × 89 × 7.9
2Ls-89 2Ls-89 2Ls-89 2Ls-127 2Ls-127 2Ls-127 2Ls-127
305 × 89 × 89 × 89 × 89 × 89 × 89 × 89
× 7.9 × 7.9 × 7.9 × 7.9 × 7.9 × 7.9 × 11
L-102 L-127 L-127 L-152
203 × 89 × 89 × 89 × 102
× 7.9 × 7.9 × 7.9 × 11
1.8 m L-102 × 89 × 7.9 L-127 × 127 × 7.9
2Ls-102 2Ls-102 2Ls-127 2Ls-127 2Ls-127 2Ls-152 2Ls-152
305 × 89 × 89 × 89 × 89 × 89 × 102 × 102
× 7.9 × 7.9 × 7.9 × 7.9 × 11 × 11 × 11
L-102 L-127 L-152
203 × 89 × 89 × 102
× 7.9 × 11 × 11
2.1 m L-102 × 89 × 7.9 L-127 × 127 × 7.9
2Ls-102 2Ls-127 2Ls-127 2Ls-152 2Ls-152
305 × 89 × 89 × 89 × 102 × 102
× 7.9 × 11 × 11 × 11 × 11
L-127 L-152
203 × 89 × 102
× 7.9 × 11
2.4 m L-127 × 89 × 7.9 L-127 × 127 × 7.9
2Ls-127 2Ls-127 2Ls-152
305 × 89 × 89 × 102
× 7.9 × 13 × 11
L-127
203 × 89
× 11
2.7 m L-127 × 89 × 11 L-127 × 127 × 11
2Ls-127 2Ls-152
305 × 152 × 102
× 11 × 11
L-152
203 × 102
× 11
3.0 m L-152 × 102 × 11 L-127 × 127 × 13
2Ls-152
305 × 102
× 11
Notes to Table 9.20.5.2.-A:
(1) The figures in the Table indicating wall thickness and angle cross-section are in mm.
(2) fs = 138 MPa., Deflection maximum = 1/700 span.
(3) See Sentence 9.20.5.2.(3.1).
(4) Omit floor load in lintel when distance to bottom of floor construction is greater than width of opening.
(5) Interior and exterior angles in 200 mm walls and interior angles in 300 mm walls are bolted together when clear span is over
1 800 mm.
(6) When masonry lighter than brick is used over interior angles floor load may be increased by the difference in weight per square metre
times the width of the opening. Not generally available.
(7) Interior angles have been designed for floor load plus brick masonry of height equal to width of opening.
Table 9.20.5.2.-B
Maximum Allowable Spans for Steel Lintels Supporting Masonry Veneer, m
Forming Part of Sentence 9.20.5.2.(3)
Minimum Angle Size, mm Maximum Allowable Spans, m
Vertical Leg Horizontal Leg Thickness 70 mm Brick 90 mm Brick 100 mm Stone
89 76 6.4 2.55 — —
89 89 6.4 2.59 2.47 2.30
102 89 6.4 2.79 2.66 2.48
127 89 7.9 3.47 3.31 3.08
127 89 11 3.64 3.48 3.24
127 89 13 3.82 3.59 3.33
152 89 11 4.06 3.82 3.54
152 89 13 4.32 4.07 3.77
152 102 13 4.37 4.12 3.82
178 102 11 4.57 4.30 3.99
178 102 13 4.87 4.59 4.25
(3.1) Steel lintels described in Sentences (2) and (3) shall
(a) have even and level bearing and shall have not less than 150 mm length of bearing at end supports, and
(b) bear on masonry, concrete or steel.
(4) Steel angle lintels supporting masonry shall be prime painted or otherwise protected from corrosion.
(5) Steel beams supporting masonry veneer and wood stud walls above openings shall conform to Table 9.20.5.2.-C.
(6) Steel beams described in Sentence (5) shall be supported at each end by a steel column, and have a minimum 6 mm
plate welded to the flange to support the masonry veneer.
Table 9.20.5.2.-C
Maximum Allowable Spans for Steel Beams Supporting Masonry Veneer, m (1)(2)(3)
Forming Part of Sentence 9.20.5.2.(5)
Section 70 mm Brick 90 mm Brick 100 mm Stone
W150 × 22 4.23 4.09 3.92
W150 × 30 4.68 4.52 4.32
W200 × 27 5.26 5.08 4.84
W200 × 31 5.57 5.37 5.11
W200 × 36 5.70 5.49 5.23
Notes to Table 9.20.5.2.-C:
(1) These spans assume that the beam supports the veneer, a wood stud wall and a maximum specified roof live load of 2.3 kN/m.
(2) Where the steel beam carries floor loads or larger roof loads, refer to Article 9.23.4.3.
(3) See Note A-Table 9.20.5.2.-C.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.20.6.Thickness and Height
9.20.6.1.Thickness of Exterior Walls permalink →
(1) Masonry exterior walls, other than cavity walls, in 1-storey buildings and the top storeys of 2- and 3-storey buildings
shall be not less than 140 mm thick, provided the walls are not more than 2.8 m high at the eaves and 4.6 m high at the
peaks of gable ends.
(2) The exterior walls of the bottom storeys of 2-storey buildings, and exterior walls of the bottom 2 storeys of 3-storey
buildings shall be not less than 190 mm thick.
(3) In exterior walls composed of more than one wythe, each wythe shall be not less than 90 mm thick.
(1) Cavity walls shall be made with not less than 90 mm wide units if the joints are raked and not less than 75 mm wide
units if the joints are not raked.
(2) The width of a cavity in a cavity wall shall be not less than 50 mm and not greater than 150 mm.
(3) The minimum thickness of cavity walls above the supporting base shall be 230 mm for the top 7.6 m and 330 mm
for the remaining portion, except that where 75 mm wide units are used, the wall height above the top of the foundation
wall shall not exceed 6 m.
9.20.6.3.Thickness of Interior Walls permalink →
(1) The thickness of loadbearing interior walls shall be determined on the basis of the maximum lateral support spacing
as provided in Sentences 9.20.10.1.(2) and (3).
(2) The thickness of interior non-loadbearing walls shall be
(a) determined on the basis of the maximum lateral support spacing as provided in Sentences 9.20.10.1.(2) and (3), and
(b) in any case, not less than 65 mm.
9.20.6.4.Masonry Veneer permalink →
(1) Except for masonry veneer where each masonry unit is supported individually by the structural backing, masonry
veneer shall consist of solid masonry units not less than 70 mm thick.
(2) Veneer described in Sentence (1) over wood-frame walls shall have not less than a 25 mm air space behind the
veneer.
(3) Masonry veneer less than 90 mm thick shall have unraked joints.
(4) Masonry veneer shall conform to Subsection 4.3.2. where the masonry units are required to be individually
supported by the structural backing.
9.20.6.5.Parapet Walls permalink →
(1) The height of parapet walls above the adjacent roof surface shall be not more than 3 times the parapet wall
thickness.
(2) A parapet wall shall be solid masonry that extends from the top of the parapet wall to not less than 300 mm below
the adjacent roof level.
(3) Where semi-solid or hollow units are used in a parapet wall, the cells of those units shall be filled with mortar, grout
or concrete.
9.20.6.6.Stone or Concrete Facings permalink →
(1) Slab and panel facings of precast concrete and natural or artificial stone shall conform to Subsection 4.3.2.
9.20.7.Chases and Recesses
9.20.7.1.Maximum Dimensions permalink →
(1) Except as permitted in Sentence 9.20.7.2.(2) and Article 9.20.7.4., the depth of any chase or recess shall not exceed
one-third the thickness of the wall, and the width of the chase or recess shall not exceed 500 mm.
9.20.7.2.Minimum Wall Thickness permalink →
(1) Except as permitted in Sentence (2) and Article 9.20.7.4., no chase or recess shall be constructed in any wall
190 mm or less in thickness.
(2) Recesses may be constructed in 190 mm walls provided they do not exceed 100 mm in depth, 750 mm in height and
500 mm in width.
9.20.7.3.Separation of Chases and Recesses permalink →
(1) Chases and recesses shall be not less than
(a) 4 times the wall thickness apart, and
(b) 600 mm away from any pilaster, cross wall, buttress or other vertical element providing required lateral support for
the wall.
9.20.7.4.Non-Conforming Chases or Recesses permalink →
(1) Chases or recesses that do not conform to the limits specified in Articles 9.20.7.1. to 9.20.7.3. shall be considered as
openings, and any masonry supported above such a chase or recess shall be supported by a lintel or arch as provided in
Article 9.20.5.2.
9.20.7.5.Chases or Recesses Cut into Walls permalink →
(1) Chases and recesses shall not be cut into walls made with hollow units after the masonry units are in place.
9.20.8.Support of Loads
9.20.8.1.Capping of Hollow Masonry Walls permalink →
(1) Except as permitted in Sentence (2), loadbearing walls of hollow masonry units supporting roof or floor framing
members shall be capped with not less than 50 mm of solid masonry or have the top course filled with concrete.
(2) Capping required in Sentence (1) may be omitted where the roof framing is supported on a wood plate not less than
38 mm by 89 mm.
9.20.8.2.Cavity Walls Supporting Framing Members permalink →
(1) Floor joists supported on cavity walls shall be supported on solid masonry units not less than 57 mm high.
(2) Floor joists described in Sentence (1) shall not project into the cavity.
(3) Roof and ceiling framing members bearing on cavity walls shall be supported on
(a) solid masonry units not less than 57 mm high that bridge the full thickness of the wall, or
(b) a wood plate not less than 38 mm thick, bearing not less than 50 mm on each wythe.
9.20.8.3.Bearing of Beams and Joists permalink →
(1) The bearing area under beams and joists shall be sufficient to carry the supported load.
(2) In no case shall the minimum length of end bearing of beams supported on masonry be less than 90 mm.
(3) The length of end bearing of floor, roof or ceiling joists supported on masonry shall be not less than 40 mm.
9.20.8.4.Support of Beams and Columns permalink →
(1) Beams and columns supported on masonry walls shall be supported on pilasters where the thickness of the masonry
wall or wythe is less than 190 mm.
(2) Not less than 190 mm depth of solid masonry or concrete shall be provided under the beam or column referred to in
Sentence (1).
(3) Pilasters required in Sentence (1) shall be bonded or tied to masonry walls.
(4) Concrete pilasters required in Sentence (1) shall be not less than 50 mm by 300 mm.
(5) Unit masonry pilasters required in Sentence (1) shall be not less than 100 mm by 290 mm.
9.20.8.5.Projection of Masonry Veneer Beyond Supporting Members permalink →
(1) Masonry veneer of solid masonry units resting on a bearing support shall not project more than one-third of the
thickness of the veneer. (See Note A-9.20.8.5.(1))
(2) Where the masonry veneer described in Sentence (1) is rough stone masonry,
(a) the projection shall be measured as the average projection of the units, and
(b) the thickness of the veneer shall be measured as the average thickness of the veneer.
9.20.9.Bonding and Tying
9.20.9.1.Joints to be Offset or Reinforced permalink →
(1) Vertical joints in adjacent masonry courses shall be offset unless each wythe of masonry is reinforced with the
equivalent of not less than 2 corrosion-resistant steel bars of 3.76 mm diam placed in the horizontal joints at vertical
intervals not exceeding 460 mm.
(2) Where joints in the reinforcing referred to in Sentence (1) occur, the bars shall be lapped not less than 150 mm.
9.20.9.2.Bonding or Tying of Other Than Masonry Veneer permalink →
(1) Except as provided in Article 9.20.9.5. regarding masonry veneer, masonry walls that consist of 2 or more wythes
shall have the wythes bonded or tied together with masonry bonding units as described in Article 9.20.9.3. or with metal
ties as described in Article 9.20.9.4.
(1) Where wythes are bonded together with masonry units, the bonding units shall comprise not less than 4% of the wall
surface area.
(2) Bonding units described in Sentence (1) shall be spaced not more than 600 mm vertically and horizontally in the
case of brick masonry and 900 mm o.c. in the case of block or tile.
(3) Units described in Sentence (1) shall extend not less than 90 mm into adjacent wythes.
(1) Where 2 or more wythes are tied together with metal ties of the individual rod type, the ties shall conform to the
requirements in Sentences (3) to (6).
(2) Other ties may be used where it can be shown that such ties provide walls that are at least as strong and as durable as
those made with the individual rod type.
(3) Metal ties of the individual rod type shall
(a) be corrosion-resistant,
(b) have a minimum cross-sectional area of not less than 17.8 mm², and
(c) have not less than a 50 mm portion bent at right angles at each end.
(4) Metal ties of the individual rod type shall
(a) extend from within 25 mm of the outer face of the wall to within 25 mm of the inner face of the wall,
(b) be completely embedded in mortar except for the portion exposed in cavity walls, and
(c) be staggered from course to course.
(5) Where 2 or more wythes in walls other than cavity walls and masonry veneer/masonry backing walls are tied
together with metal ties of the individual rod type, the space between wythes shall be completely filled with mortar.
(6) Ties described in Sentence (5) shall be
(a) located within 300 mm of openings and spaced not more than 900 mm apart around openings, and
(b) spaced not more than 900 mm apart horizontally and 460 mm apart vertically at other locations.
(7) Except as required in Sentences (8) and (9), where the inner and outer wythes of cavity walls are tied with individual
wire ties, the ties shall be spaced not more than 900 mm apart horizontally and 400 mm apart vertically.
(8) Within 100 mm of the bottom of each floor or roof assembly where the cavity extends below the assemblies, the ties
described in Sentence (7) shall be spaced not more than 600 mm apart horizontally.
(9) Within 300 mm of any openings, the ties described in Sentence (7) shall be spaced not more than 900 mm apart.
9.20.9.5.Ties for Masonry Veneer permalink →
(1) Masonry veneer 70 mm or more in thickness and resting on a bearing support shall be tied to masonry backing or to
wood framing members with straps that are
(a) corrosion-resistant,
(b) not less than 0.76 mm thick,
(c) not less than 22 mm wide,
(d) shaped to provide a key with the mortar,
(e) pre-bent during manufacture to a right angle within 6 mm of the fastener hole,
(f) fastened with
(i) corrosion-resistant wood screws conforming to Sentence 9.23.3.1.(3) that have a minimum diameter of
4.16 mm (No. 8) and a wood penetration of not less than 38 mm, or
(ii) corrosion-resistant common spiral nails conforming to Sentence 9.23.3.1.(1) that are not less than 76 mm long
and have a wood penetration of not less than 63 mm, and
(g) spaced in accordance with Table 9.20.9.5.
Table 9.20.9.5.
Veneer Tie Spacing
Forming Part of Sentence 9.20.9.5.(1)
Maximum Vertical Spacing, mm Maximum Horizontal Spacing, mm
400 800
500 600
600 400
(2) Where hot-dipped, zinc-coated straps are used to meet the requirements of Sentence (1), they shall be pre-bent and
pre-drilled or pre-punched prior to hot-dip, zinc-coated galvanizing.
(3) Masonry veneer individually supported by masonry or wood-frame backing shall be secured to the backing in
conformance with Subsection 4.3.2.
(4) The straps described in Sentence (1) may be installed against one of the sheathings listed in Table 9.23.17.2.-A
provided that
(a) the tie is in contact with the exterior surface of the sheathing, and
(b) the sheathing beneath the tie is not compressed.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.20.9.6.Reinforcing for Glass Block permalink →
(1) Glass block shall have horizontal joint reinforcement of two corrosion-resistant bars of not less than 3.76 mm diam
or expanded metal strips not less than 75 mm wide
(a) spaced at vertical intervals of not more than 600 mm for units 190 mm or less in height, and
(b) installed in every horizontal joint for units higher than 190 mm.
(2) Reinforcement required in Sentence (1) shall be lapped not less than 150 mm.
9.20.10.Lateral Support
9.20.10.1.Lateral Support Required permalink →
(1) Masonry walls shall be laterally supported by floor or roof construction or by intersecting masonry walls or
buttresses.
(2) The spacing of supports required in Sentence (1) shall be not more than
(a) 20 times the wall thickness for all loadbearing walls and exterior non-loadbearing walls, and
(b) 36 times the wall thickness for interior non-loadbearing walls.
(3) In applying Sentence (2), the thickness of cavity walls shall be taken as the greater of
(a) two-thirds of the sum of the thicknesses of the wythes, or
(b) the thickness of the thicker wythe.
(4) Floor and roof structural elements providing lateral support for walls as required in Sentence (1) shall be constructed
to transfer lateral loads to walls or buttresses approximately at right angles to the laterally supported walls.
9.20.11.Anchorage of Roofs, Floors and Intersecting Walls
9.20.11.1.Anchorage to Floor or Roof Assemblies where Masonry Walls Require permalink →
Lateral Support
(1) Where required to receive lateral support (See Subsection 9.20.10.), masonry walls shall be anchored to each floor
or roof assembly at maximum intervals of 2 m, except that anchorage to floor joists not more than 1 m above grade may
be omitted.
(2) Anchors required in Sentence (1) shall be corrosion-resistant and be not less than the equivalent of 40 mm by
4.76 mm thick steel straps.
(3) Anchors required in Sentence (1) shall be shaped to provide a mechanical key with the masonry and shall be
securely fastened to the horizontal support to develop the full strength of the anchor.
(4) When joists are parallel to the wall, anchors required in Sentence (1) shall extend across not less than 3 joists.
9.20.11.2.Bonding and Tying Intersecting Masonry Walls where Walls Require permalink →
Lateral Support
(1) Where required to provide lateral support, intersecting walls shall be bonded or tied together.
(2) Where bonding is used to satisfy the requirements of Sentence (1), 50% of the adjacent masonry units in the
intersecting wall, distributed uniformly over the height of the intersection, shall be embedded in the laterally supported
wall.
(3) Where tying is used to satisfy the requirements of Sentence (1), the ties shall be
(a) corrosion-resistant metal,
(b) equivalent to not less than 4.76 mm by 40 mm steel strapping,
(c) spaced not more than 800 mm o.c. vertically, and
(d) shaped at both ends to provide sufficient mechanical key to develop the strength of the ties.
9.20.11.3.Anchoring Intersecting Wood-Frame Walls to Masonry Walls permalink →
(1) Wood-frame walls shall be tied to intersecting masonry walls with not less than 4.76 mm diam corrosion-resistant
steel rods spaced not more than 900 mm o.c. vertically.
(2) Ties required in Sentence (1) shall be anchored to the wood framing at one end and shaped to provide a mechanical
key at the other end to develop the strength of the tie.
9.20.11.4.Anchoring Wood-Frame Roof Systems to Masonry Walls permalink →
(1) Except as permitted in Sentence (2), roof systems of wood-frame construction shall be tied to exterior masonry walls
by not less than 12.7 mm diam anchor bolts,
(a) spaced not more than 2.4 m apart,
(b) embedded not less than 90 mm into the masonry, and
(c) fastened to a rafter plate of not less than 38 mm thick lumber.
(2) The roof system described in Sentence (1) is permitted to be anchored by nailing the wall furring strips to the side of
the rafter plate.
9.20.11.5.Anchoring Masonry Cornices, Sills and Trim to Masonry Walls permalink →
(1) Cornices, sills or other trim of masonry material which project beyond the wall face shall have not less than 65% of
their mass, but not less than 90 mm, within the wall or shall be adequately anchored to the wall with corrosion-resistant
anchors.
9.20.11.6.Anchoring to Masonry Piers permalink →
(1) Where anchor bolts are to be placed in the top of a masonry pier, the pier shall conform to the requirements of
Sentence 9.15.2.3.(4) and shall be capped with concrete or reinforced masonry not less than 200 mm thick.
9.20.12.Corbelling
(1) All corbelling shall consist of solid masonry units.
(2) The units referred to in Sentence (1) shall be corbelled so that the horizontal projection of any unit does not exceed
25 mm and the total projection does not exceed one-third of the total wall thickness.
9.20.12.2.Corbelling for Cavity Walls permalink →
(1) Cavity walls of greater thickness than the foundation wall on which they rest shall not be corbelled but may project
25 mm over the outer face of the foundation wall disregarding parging.
(2) Where the foundation wall referred to in Sentence (1) is unit masonry, it is permitted to be corbelled to meet flush
with the inner face of a cavity wall provided
(a) the projection of each course does not exceed half the height or one-third the thickness of the corbelled unit, and
(b) the total corbel does not exceed one-third of the foundation wall thickness.
(See Note A-9.20.12.2.(2))
9.20.12.3.Corbelling for Masonry Veneer permalink →
(1) Masonry veneer resting on a bearing support shall not project more than 25 mm beyond the supporting base where
the veneer is not less than 90 mm thick, and 12 mm beyond the supporting base where the veneer is less than 90 mm
thick.
(2) In the case of rough stone veneer, the projection, measured as the average projection of the stone units, shall not
exceed one-third the bed width beyond the supporting base.
9.20.13.Control of Rainwater Penetration
9.20.13.1.Materials for Flashing permalink →
(1) Materials used for flashing shall conform to Table 9.20.13.1.
(2) Aluminum flashing in contact with masonry or concrete shall be effectively coated or separated from the masonry or
concrete by an impervious membrane.
Table 9.20.13.1.
Flashing Materials
Forming Part of Sentence 9.20.13.1.(1)
Minimum Thickness, mm
Material
Exposed Flashing Concealed Flashing
Aluminum 0.48 —
Copper 0.46 0.46
Copper or aluminum laminated to felt or kraft paper — 0.05
Galvanized steel 0. 33 0.33
Lead sheet 1.73 1.73
Polyethylene — 0.50
Roll roofing, Type S — standard
Zinc 0.46 0.46
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.20.13.2.Fastening of Flashing permalink →
(1) Fastening devices for flashing shall be corrosion-resistant and, where metal flashing is used, shall be compatible
with the flashing with respect to galvanic action.
9.20.13.3.Location of Flashing permalink →
(1) Flashing shall be installed in masonry and masonry veneer walls
(a) beneath jointed masonry window sills,
(b) over the back and top of parapet walls,
(c) over the heads of glass block panels,
(d) beneath weep holes, and
(e) over the heads of window or door openings in exterior walls when the vertical distance between the top of a window
or door frame and the bottom edge of the eave exceeds one-quarter of the horizontal eave overhang.
(2) Throughwall flashing shall be provided in a masonry veneer wall such that any moisture that accumulates in the air
space will be directed to the exterior of the building.
9.20.13.4.Extension of Flashing permalink →
(1) When installed beneath jointed masonry window sills and jointed masonry copings or over the heads of openings,
flashing shall extend from the front edge of the masonry up behind the sill or lintel.
(2) A flashing may be omitted when the masonry at the sill of a wall opening or the top of a wall is protected by an
impervious non-jointed masonry coping that conforms to Article 9.20.13.12.
9.20.13.5.Flashing for Weep Holes in Masonry Veneer/Masonry Walls permalink →
(1) Flashing beneath weep holes in cavity walls and masonry veneer/masonry backing walls shall
(a) be bedded not less than 25 mm in the inside wythe,
(b) extend to not less than 5 mm beyond the outer face of the building element below the flashing, and
(c) be installed with a nominally horizontal slope toward the outside wythe.
9.20.13.6.Flashing for Weep Holes in Masonry Veneer permalink →
(1) Flashing beneath weep holes in masonry veneer over masonry backing walls shall conform to the flashing
requirements for cavity walls and masonry veneer/masonry backing walls in Article 9.20.13.5.
(2) Flashing beneath weep holes in masonry veneer over wood frame walls shall be installed so that it extends from a
point not less than 5 mm beyond the outer face of the building element below the flashing to a point 150 mm up the
wood-frame wall.
(3) Where the frame wall is sheathed with a sheathing membrane, a non-wood-based rigid exterior insulating sheathing
or a semi-rigid insulating sheathing with an integral sheathing membrane, the flashing shall be installed behind the
sheathing membrane or insulating sheathing.
(4) Flashing described in Sentence (2) is permitted to conform to the requirements for concealed flashing in
Table 9.20.13.1.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.20.13.7.Flashing Joints permalink →
(1) Joints in flashing shall be made watertight.
9.20.13.8.Required Weep Holes permalink →
(1) Weep holes spaced not more than 800 mm apart shall be provided at the bottom of
(a) cavities in cavity walls, and
(b) cavities or air spaces in masonry veneer walls.
(2) The cavities or air spaces described in Sentence (1) shall include those above lintels over window and door openings
required to be flashed in conformance with Article 9.20.13.3.
(3) The weep holes required in Sentence (1) shall be in a location such that any water that collects in the cavity or space
will be directed to the exterior of the building.
9.20.13.9.Protection of Interior Finish permalink →
(1) Except as provided in Sentence (3), where the interior finish of the exterior walls of a building is a type that may be
damaged by moisture, exterior masonry walls, other than cavity walls or walls that are protected for their full height by a
roof of a carport or porch, shall be
(a) parged on the interior surface, and
(b) covered with No. 15 breather-type asphalt-saturated paper conforming to CAN/CGSB-51.32-M, “Sheathing,
Membrane, Breather Type,” and shall be lapped not less than 100 mm at the joints.
(2) In situations described in Sentence (1), flashing shall be provided where water will accumulate, to lead it to the
exterior.
(3) Where insulation effectively limits the passage of water vapour and is applied by a waterproof adhesive or by mortar
directly to the masonry, the requirements for sheathing paper do not apply. (See Note A-9.20.13.9.(3))
9.20.13.10.Mortar Droppings permalink →
(1) Cavity walls shall be constructed so that mortar droppings are prevented from forming a bridge to allow the passage
of rainwater across the cavity.
9.20.13.11.Caulking at Door and Window Frames permalink →
(1) The junction of door and window frames with masonry shall be caulked in conformance with Subsection 9.27.4.
9.20.13.12.Drips Beneath Window Sills permalink →
(1) Except for wall openings located less than 150 mm above ground level, where a concealed flashing is not installed
beneath window and door sills, such sills shall be provided with an outward slope and a drip located not less than 25 mm
from the wall surface.
9.20.14.Protection During Work
9.20.14.1.Laying Temperature of Mortar and Masonry permalink →
(1) Mortar and masonry shall be maintained at a temperature not below 5°C during installation and for not less than
48 h after installation.
(2) No frozen material shall be used in mortar mix.
9.20.14.2.Protection from Weather permalink →
(1) The top surface of uncompleted masonry exposed to the weather shall be completely covered with a waterproofing
material when construction is not in progress.
9.20.15.Reinforcement for Earthquake Resistance
9.20.15.1.Amount of Reinforcement permalink →
(1) Where reinforcement is required in this Section, masonry walls shall be reinforced horizontally and vertically with
steel having a total cross-sectional area of not less than 0.002 times the horizontal cross-sectional area of the wall, so that
not less than one-third of the required steel area is installed either horizontally or vertically and the remainder in the other
direction.
9.20.15.2.Installation Standard permalink →
(1) Where reinforcement for masonry is required in this Section, it shall be installed in conformance with the
requirements for reinforced masonry as contained in CAN/CSA-A371, “Masonry construction for buildings.”
9.20.16.Corrosion Resistance
9.20.16.1.Corrosion Resistance of Connectors permalink →
(1) Carbon steel connectors required to be corrosion-resistant shall be galvanized to at least the minimum standards in
Table 9.20.16.1.
Table 9.20.16.1.
Minimum Requirements for Galvanizing
Forming Part of Sentence 9.20.16.1.(1)
Connector Material ASTM Standard Coating Class or Thickness
Wire ties and continuous reinforcing (hot-dipped galvanizing) ASTM A153 / A153M Class B2 or 458 g/m²
Hardware and bolts ASTM A153 / A153M See ASTM A153 / A153M
Strip, plate, bars, and rolled sections (not less than 3.18 mm thick) ASTM A123 / A123M 610 g/m²
Sheet (less than 3.18 mm thick) ASTM A123 / A123M 460 g/m² on material 0.76 mm thick(1)
Notes to Table 9.20.16.1.:
(1) ASTM A123 / A123M does not apply to metal less than 0.76 mm thick. Galvanizing coatings may be interpolated for thicknesses
between 3.18 mm and 0.76 mm.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.20.17.Above-Ground Flat Insulating Concrete Form Walls
9.20.17.1.Thickness of Flat Insulating Concrete Form Walls permalink →
(1) The thickness of concrete in flat insulating concrete form walls not in contact with the ground shall be
(a) not less than 140 mm, and
(b) constant for the entire height of the wall.
9.20.17.2.Reinforcement for Flat Insulating Concrete Form Walls permalink →
(1) Horizontal reinforcement in above-grade flat insulating concrete form walls shall
(a) consist of
(i) one 10M bar placed not more than 300 mm from the top of the wall, and
(ii) 10M bars spaced not more than 600 mm o.c., and
(b) be placed in the middle third of the wall section.
(2) Vertical reinforcement in above-grade flat insulating concrete form walls shall
(a) consist of 10M bars spaced not more than 400 mm o.c., and
(b) be placed in the middle third of the wall section.
(3) Vertical reinforcement required by Sentence (2) and interrupted by wall openings shall be placed not more than
600 mm from each side of the opening.
9.20.17.3.Openings in Non-Loadbearing Flat Insulating Concrete Form Walls permalink →
(1) No openings shall occur within 1 200 mm of interior and exterior corners of exterior non-loadbearing flat insulating
concrete form walls.
(2) Portions of walls over openings in non-loadbearing flat insulating concrete form walls shall have a minimum depth
of concrete of not less than 200 mm across the width of the opening.
(3) Openings more than 600 mm but not more than 3 000 mm in width in non-loadbearing flat insulating concrete form
walls shall be reinforced at the top and bottom with one 10M bar.
(4) Openings more than 3 000 mm in width in non-loadbearing flat insulating concrete form walls shall be reinforced
on all four sides with two 10M bars.
(5) Reinforcing bars described in Sentences (3) and (4) shall extend 600 mm beyond the edges of the opening.
(6) The cumulative width of openings in non-loadbearing flat insulating concrete form walls shall be not more than
70% of the length of any wall.
9.20.17.4.Openings in Loadbearing Flat Insulating Concrete Form Walls permalink →
(1) No openings shall occur within 1 200 mm of interior and exterior corners of exterior loadbearing flat insulating
concrete form walls.
(2) In loadbearing flat insulating concrete form walls, lintels shall be provided over all openings wider than 900 mm.
(3) Lintels described in Sentence (2) shall be constructed in accordance with Span Table 9.20.17.4.-A, 9.20.17.4.-B or
9.20.17.4.-C.
(4) Lintels described in Sentence (2) over openings wider than 1 200 mm shall be reinforced for shear with 10M stirrups
at a maximum spacing of half the distance from the bottom reinforcing bar to the top of the lintel.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.20.17.5.Framing Supported on Flat Insulating Concrete Form Walls permalink →
(1) Floor joists supported on the side of flat insulating concrete form walls shall be supported with joist hangers secured
to wood ledger boards.
(2) The ledger boards referred to in Sentence (1) shall be not less than
(a) 38 mm thick, and
(b) the depth of the floor joists.
(3) Anchor bolts shall be used to secure ledger boards to flat insulating concrete form walls and shall be
(a) embedded in the wall to a depth not less than 100 mm, and
(b) spaced in accordance with Table 9.20.17.5.
(4) Floor joists and building frames supported on the top of flat insulating concrete form walls shall be anchored in
conformance with Article 9.23.6.1.
Table 9.20.17.5.
Maximum Anchor Bolt Spacing for the Connection of Floor Ledgers to Flat Insulating Concrete Form Walls
Forming Part of Sentence 9.20.17.5.(3)
Maximum Anchor Bolt Spacing, mm
Maximum Clear Floor Span, m
Staggered 12.7 mm Diameter Anchor Bolts Staggered 16 mm Diameter Anchor Bolts
2.44 450 500
3.00 400 450
4.00 300 400
5.00 275 325
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.20.17.6.Anchoring of Roof Framing to Top of Flat Insulating Concrete permalink →
Form Walls
(1) Roof framing supported on the top of flat insulating concrete form walls shall be fixed to the top plates, which shall
be anchored to the wall with anchor bolts
(a) not less than 12.7 mm in diameter, and
(b) spaced not more than 1 200 mm o.c.
(2) The anchor bolts described in Sentence (1) shall be placed in the centre of the flat insulating concrete form wall and
shall be embedded no less than 100 mm into the concrete.
(3) Attachment of roof framing to wood top plates shall be in accordance with Table 9.23.3.4.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.20.17.7.Protection from Precipitation and Damage permalink →
(1) Above-ground flat insulating concrete form walls shall be protected from precipitation and damage in conformance
with Section 9.27.
Understand any provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Try BUILDAiD Beta
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.