9.20.15.1.Amount of Reinforcement
(1) Where reinforcement is required in this Section, masonry walls shall be reinforced horizontally and vertically with
steel having a total cross-sectional area of not less than 0.002 times the horizontal cross-sectional area of the wall, so that
not less than one-third of the required steel area is installed either horizontally or vertically and the remainder in the other
direction.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.