9.20.17.1.Thickness of Flat Insulating Concrete Form Walls
(1) The thickness of concrete in flat insulating concrete form walls not in contact with the ground shall be
(a) not less than 140 mm, and
(b) constant for the entire height of the wall.
← Previous9.20.16.1. Corrosion Resistance of ConnectorsNext →9.20.17.2. Reinforcement for Flat Insulating Concrete Form
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.