9.20.13.3.Location of Flashing
(1) Flashing shall be installed in masonry and masonry veneer walls
(a) beneath jointed masonry window sills,
(b) over the back and top of parapet walls,
(c) over the heads of glass block panels,
(d) beneath weep holes, and
(e) over the heads of window or door openings in exterior walls when the vertical distance between the top of a window
or door frame and the bottom edge of the eave exceeds one-quarter of the horizontal eave overhang.
(2) Throughwall flashing shall be provided in a masonry veneer wall such that any moisture that accumulates in the air
space will be directed to the exterior of the building.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.