9.20.11.3.Anchoring Intersecting Wood-Frame Walls to Masonry Walls
(1) Wood-frame walls shall be tied to intersecting masonry walls with not less than 4.76 mm diam corrosion-resistant
steel rods spaced not more than 900 mm o.c. vertically.
(2) Ties required in Sentence (1) shall be anchored to the wood framing at one end and shaped to provide a mechanical
key at the other end to develop the strength of the tie.
← Previous9.20.11.2. Bonding and Tying Intersecting Masonry Walls wheNext →9.20.11.4. Anchoring Wood-Frame Roof Systems to Masonry Wal
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.