PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.20.17.2.Reinforcement for Flat Insulating Concrete Form Walls
(1) Horizontal reinforcement in above-grade flat insulating concrete form walls shall
(a) consist of
(i) one 10M bar placed not more than 300 mm from the top of the wall, and
(ii) 10M bars spaced not more than 600 mm o.c., and
(b) be placed in the middle third of the wall section.
(2) Vertical reinforcement in above-grade flat insulating concrete form walls shall
(a) consist of 10M bars spaced not more than 400 mm o.c., and
(b) be placed in the middle third of the wall section.
(3) Vertical reinforcement required by Sentence (2) and interrupted by wall openings shall be placed not more than
600 mm from each side of the opening.
← Previous9.20.17.1. Thickness of Flat Insulating Concrete Form WallsNext →9.20.17.3. Openings in Non-Loadbearing Flat Insulating Conc
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.