PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.20.13.6.Flashing for Weep Holes in Masonry Veneer
(1) Flashing beneath weep holes in masonry veneer over masonry backing walls shall conform to the flashing
requirements for cavity walls and masonry veneer/masonry backing walls in Article 9.20.13.5.
(2) Flashing beneath weep holes in masonry veneer over wood frame walls shall be installed so that it extends from a
point not less than 5 mm beyond the outer face of the building element below the flashing to a point 150 mm up the
wood-frame wall.
(3) Where the frame wall is sheathed with a sheathing membrane, a non-wood-based rigid exterior insulating sheathing
or a semi-rigid insulating sheathing with an integral sheathing membrane, the flashing shall be installed behind the
sheathing membrane or insulating sheathing.
(4) Flashing described in Sentence (2) is permitted to conform to the requirements for concealed flashing in
Table 9.20.13.1.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
← Previous9.20.13.5. Flashing for Weep Holes in Masonry Veneer/MasonrNext →9.20.13.7. Flashing Joints
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.