9.20.13.4.Extension of Flashing
(1) When installed beneath jointed masonry window sills and jointed masonry copings or over the heads of openings,
flashing shall extend from the front edge of the masonry up behind the sill or lintel.
(2) A flashing may be omitted when the masonry at the sill of a wall opening or the top of a wall is protected by an
impervious non-jointed masonry coping that conforms to Article 9.20.13.12.
← Previous9.20.13.3. Location of FlashingNext →9.20.13.5. Flashing for Weep Holes in Masonry Veneer/Masonr
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.