PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.20.8.4.Support of Beams and Columns
(1) Beams and columns supported on masonry walls shall be supported on pilasters where the thickness of the masonry
wall or wythe is less than 190 mm.
(2) Not less than 190 mm depth of solid masonry or concrete shall be provided under the beam or column referred to in
Sentence (1).
(3) Pilasters required in Sentence (1) shall be bonded or tied to masonry walls.
(4) Concrete pilasters required in Sentence (1) shall be not less than 50 mm by 300 mm.
(5) Unit masonry pilasters required in Sentence (1) shall be not less than 100 mm by 290 mm.
← Previous9.20.8.3. Bearing of Beams and JoistsNext →9.20.8.5. Projection of Masonry Veneer Beyond Supporting M
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.