3.3.1.All Floor Areas
3.3.1.1.Separation of Suites permalink →
(1) Except as permitted by Sentences (2) and (3), each suite in other than business and personal services occupancies
shall be separated from adjoining suites by a fire separation having a fire-resistance rating not less than 1 h. (See also
Subsection 3.3.3. for care, care and treatment or detention occupancies, Article 3.3.4.2. for residential occupancies, and
Article 3.1.8.7. for fire dampers.)
(2) The fire-resistance rating of the fire separation required by Sentence (1) is permitted to be less than 1 h but not less
than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for
(a) the floor assembly above the floor area, or
(b) the floor assembly below the floor area, if there is no floor assembly above.
(3) Occupancies that are served by public corridors conforming to Clause 3.3.1.4.(4)(b) in a building that is sprinklered
throughout, are not required to be separated from one another by fire separations provided the occupancies are
(a) suites of business and personal services occupancy,
(b) fast food vending operations that do not provide seating for customers,
(c) suites of mercantile occupancy, or
(d) any combination of these occupancies.
3.3.1.2.Hazardous Substances, Equipment and Processes permalink →
(1) Except as provided in Subsections 3.3.5. and 3.3.6., the storage, handling and use of the hazardous substances shall
be in conformance with
(a) the Fire Code made under the Fire Protection and Prevention Act, 1997, or
(b) the CCBFC NRCC-CONST-56437E, “National Fire Code of Canada,” in the absence of regulations referred to in
Clause (a).
(See Note A-3.3.1.2.(1))
(2) Systems for the ventilation of cooking equipment that is not within a dwelling unit and is used in processes
producing grease-laden vapours shall be designed and installed in conformance with Articles 3.6.3.5., 6.3.1.6. and 6.9.1.3.
(See Note A-3.3.1.2.(2))
(3) A fuel-fired appliance shall not be installed in a corridor serving as an access to exit.
3.3.1.3.Means of Egress permalink →
(1) Access to exit within floor areas shall conform to Subsections 3.3.2. to 3.3.5., in addition to the requirements of this
Subsection.
(2) If a podium, terrace, platform or contained open space is provided, egress requirements shall conform to the
appropriate requirements of Sentence 3.3.1.5.(1) for rooms and suites.
(3) Means of egress shall be provided from every roof that is intended for occupancy, and from every podium, terrace,
platform or contained open space.
(4) At least two separate means of egress shall be provided from a roof, used or intended for an occupant load more
than 60, to stairs designed in conformance with the requirements regarding exit stairs stated in Section 3.4.
(5) A rooftop enclosure shall be provided with an access to exit that leads to an exit
(a) at the roof level, or
(b) on the storey immediately below the roof.
(6) A rooftop enclosure which is more than 200 m2 in area shall be provided with at least 2 means of egress.
(7) Two points of egress shall be provided for a service space referred to in Sentence 3.2.1.1.(8) if
(a) the area is more than 200 m2, or
(b) the travel distance measured from any point in the service space to a point of egress is more than 25 m.
(8) Except as required by Sentence 3.3.4.4.(8) and permitted by Sentences 3.3.4.4.(5) and (6), each suite in a floor area
that contains more than one suite shall have
(a) an exterior exit doorway, or
(b) a doorway,
(i) into a public corridor, or
(ii) to an exterior passageway.
(9) Except as permitted by this Section and by Sentence 3.4.2.1.(2), at the point where a doorway referred to in
Sentence (8) opens onto a public corridor or exterior passageway, it shall be possible to go in opposite directions to each
of 2 separate exits.
(10) Means of egress from a roof for personnel servicing roof top equipment or for a below ground service room that is
not normally occupied, is permitted to be provided by stairways or fixed ladders.
3.3.1.4.Public Corridor Separations permalink →
(1) Except as otherwise required by this Part or as permitted by Sentence (4), a public corridor shall be separated from
the remainder of the storey by a fire separation.
(2) Except as permitted by Sentence (3) and Clauses (4)(a) and (b), the fire separation between a public corridor and
the remainder of the storey shall have a fire-resistance rating not less than 45 min.
(3) If a storey is sprinklered throughout, no fire-resistance rating is required for a fire separation between a public
corridor and the remainder of the storey, provided the corridor does not serve a care, care and treatment, detention or
residential occupancy. (See Note A-3.1.8.1.(1)(b))
(4) No fire separation is required in a sprinklered floor area between a public corridor and
(a) except as required by Sentences 3.3.3.5.(9) and 3.3.4.2.(1) and notwithstanding Sentence 3.4.2.4.(2), the remainder
of a storey, provided the travel distance from any part of the floor area to an exit is not more than 45 m.,
(b) a room or suite, provided the public corridor complies with Sentence 3.3.1.9.(4) and Clause 3.4.2.5.(1)(d), or
(c) a space containing plumbing fixtures required by Subsection 3.7.4. provided the space and the public corridor are
separated from the remainder of the storey by a fire separation having a fire-resistance rating not less than that
required between the public corridor and the remainder of the storey.
3.3.1.5.Egress Doorways permalink →
(1) Except for dwelling units, a minimum of 2 egress doorways located so that one doorway could provide egress from
the room or suite as required by Article 3.3.1.3. if the other doorway becomes inaccessible to the occupants due to a fire
that originates in the room or suite, shall be provided for every room and every suite
(a) whose area is more than 15 m2 and is used for
(i) a high-hazard industrial occupancy, or
(ii) a hazardous room,
(b) intended for an occupant load more than 60,
(c) in a floor area that is not sprinklered throughout and
(i) the area of a room or suite is more than the value in Table 3.3.1.5.-A, or
(ii) the travel distance within the room or suite to the nearest egress doorway, is more than the value in Table
3.3.1.5.-A,
(d) in a floor area that is sprinklered throughout and does not contain a high-hazard industrial occupancy and
(i) the travel distance to an egress doorway is more than 25 m, or
(ii) the area of the room or suite is more than the value in Table 3.3.1.5.-B, or
(e) where the area of the room is more than 100 m 2 and it is a hazardous classroom in elementary or secondary school.
(2) Where 2 egress doorways are required by Sentence (1), they shall be placed at a distance from one another equal to
or greater than one third of the maximum overall diagonal dimension of the area to be served, measured as the shortest
distance that smoke would have to travel between the nearest required egress doors.
Table 3.3.1.5.-A
Egress in Floor Area Not Sprinklered Throughout
Forming Part of Sentence 3.3.1.5.(1)
Occupancy of Room or Suite Maximum Area of Room or Suite, m2 Maximum Distance to Egress Doorway, m
Group A 150 15
Group C 100(1) 15(1)
Group D 200 25
Group E 150 15
Group F, Division 2 150 10
Group F, Division 3 200 15
Notes to Table 3.3.1.5.-A:
(1) See Article 3.3.4.4. for dwelling units.
Table 3.3.1.5.-B
Egress in Floor Area Sprinklered Throughout
Forming Part of Sentence 3.3.1.5.(1)
Occupancy of Room or Suite Maximum Area of Room or Suite, m2
Group A 200
Group B, Division 1 100
Group B, Division 2 or 3
sleeping rooms 100
other than sleeping rooms 200
Group C 150(1)
Group D 300
Group E 200
Group F, Division 2 200
Group F, Division 3 300
Notes to Table 3.3.1.5.-B:
(1) See Article 3.3.4.4. for dwelling units.
(3) Every room containing an assembly occupancy serving a hotel, and located in the building containing the hotel, shall
be provided with no fewer than
(a) three separate egress doorways from the room where the occupant load is more than 600 persons, and
(b) four separate egress doorways from the room where the occupant load is more than 1 000 persons
(4) Each egress doorway in Sentence (4) shall be considered as contributing not more than,
(a) one-third of the required width where three egress doorways are required, and
(b) one-fourth of the required width where four egress doorways are required.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
3.3.1.6.Travel Distance permalink →
(1) If more than one egress doorway is required from a room or suite referred to in Article 3.3.1.5., the travel distance
within the room or suite to the nearest egress doorway shall not exceed the maximum travel distances specified in Clauses
3.4.2.5.(1)(a), (b), (c) and (f) for exits.
3.3.1.7.Protection on Floor Areas with a Barrier-Free Path of Travel permalink →
(1) Except as provided in Sentences (1.1) and (1.2), every floor area above or below the first storey that has a barrier-
free path of travel shall
(a) be served by an elevator
(i) conforming to Sentences 3.2.6.5.(4) to (6),
(ii) protected against fire in conformance with Clause 3.2.6.5.(3)(b) or (c), and
(iii) in a building over 3 storeys in building height, protected against smoke movement so that the hoistway will
not contain more than 1% by volume of contaminated air from a fire floor during a period of 2 h after the start
of a fire, assuming an outdoor temperature equal to the January design temperature on a 2.5% basis
determined in conformance with MMAH Supplementary Standard SB-1, “Climatic and Seismic Data,” or
(b) be divided into at least 2 zones by fire separations conforming to Sentences (2) and (3) and 3.1.8.5.(6) so that, (See
Note A-3.3.1.7.(1)(b))
(i) persons with physical disabilities can be accommodated in each zone,
(ii) the travel distance from any point in one zone to a doorway leading to another zone shall be not more than the
value for travel distance permitted by Sentence 3.4.2.5.(1) for the occupancy classification of the zone, and
(iii) a barrier-free path of travel is provided to an exit.
(See Note A-3.3.1.7.(1))
(1.1) In residential occupancies, the requirements of Sentence (1) are waived if a balcony conforming to Sentence (4) is
provided for each suite, except for suites on the storey containing the barrier-free entrance described in Article 3.8.1.2.
(1.2) The requirements of Sentences (1) and (1.1) are waived when the building is sprinklered throughout.
(2) Except as permitted by Sentence (3), the fire separations referred to in Clause (1)(b) shall have a fire-resistance
rating not less than 1 h.
(3) The fire-resistance rating of the fire separations referred to in Clause (1)(b) is permitted to be less than 1 h but not
less than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for
(a) the floor assembly above the floor area, or
(b) the floor assembly below the floor area, if there is no floor assembly above.
(4) A balcony required by Sentence (1.1) shall
(a) be provided with a doorway having a clear width of not less that 800 mm when the door is in the open position,
(b) have no projection above the walking surface more than 13 mm,
(c) be not less than 1.5 m deep from the outside face of the exterior wall to the inside edge of the balcony, and
(d) provide not less than 0.5 m2 for each occupant of the suite.
3.3.1.8.Headroom and Protruding Objects permalink →
(1) Except within the floor area of a storage garage, the minimum headroom clearance in every access to exit shall
conform to the requirements of Article 3.4.3.4. for exits. (See also Sentence 3.3.5.4.(5))
(2) Except as permitted by Sentence (3) and except for paths of travel in service rooms and dwelling units, protruding
building elements located within 1 980 mm of the floor shall not project more than 100 mm horizontally into paths of
travel in a manner that would create a hazard. (See Note A-3.3.1.8.(2) and (3))
(3) The horizontal projection of a protruding building element referred to in Sentence (2) is permitted to be more than
100 mm, provided the clearance between the protruding element and the floor is less than 680 mm. (See Note A-
3.3.1.8.(2) and (3))
(1) The minimum width of a public corridor shall be 1 100 mm.
(2) Except as required by Sentences 3.3.3.3.(2) and (3), the minimum unobstructed width shall be 1 100 mm for every
(a) corridor used by the public,
(b) corridor serving classrooms, and
(c) corridor in a Group B, Division 2 or 3 occupancy where the corridor
(i) serves a service room,
(ii) serves an administrative area,
(iii) will not be used by non-ambulatory outpatients, or
(iv) will not be used by non-ambulatory residents.
(3) If a corridor contains an occupancy, the occupancy shall not reduce the unobstructed width of the corridor to less
than its required width.
(4) If a public corridor conforming to Clause 3.4.2.5.(1)(d) contains an occupancy,
(a) the occupancy shall be located so that for pedestrian travel there is an unobstructed width not less than 3 m at all
times adjacent and parallel to all rooms and suites that front onto the public corridor, and
(b) the combined area of all occupancies in the public corridor shall be not more than 15% of the area of the public
corridor.
(5) Except as provided in Sentence 3.3.3.3.(1), a dead-end corridor shall conform to Sentences (6) to (12).
(6) A dead-end corridor is permitted in an assembly occupancy where there is a second and separate egress doorway
from each room or suite not leading into a dead-end corridor.
(7) Except as provided in Sentence 3.3.4.11.(10) and except for corridors served by a single exit as described in
Sentence 3.3.4.4.(6), a dead-end public corridor is permitted in a residential occupancy provided it is not more than 6 m
long.
(8) Dead-end corridors in Sentence (9) shall contain no door openings to service rooms containing fuel-fired appliances
or rooms that may be considered a hazard.
(9) A dead-end public corridor is permitted in a business and personal services occupancy where
(a) the dead-end corridor
(i) serves an occupant load of not more than 30 persons,
(ii) is not more than 9 m long, and
(iii) is provided with doors having self-closing devices, or
(b) there is a second and separate egress doorway from each room or suite not leading into a dead-end corridor.
(10) A dead-end corridor is permitted in a mercantile occupancy where
(a) the dead-end corridor
(i) serves an occupant load of not more than 30 persons,
(ii) is not more than 9 m long, and
(iii) is provided with doors having self-closing devices, or
(b) there is a second and separate egress doorway from each room or suite not leading into a dead-end corridor.
(11) A dead-end corridor is permitted in a low- or medium-hazard industrial occupancy where
(a) the dead-end corridor
(i) serves an occupant load of not more than 30 persons,
(ii) is not more than 9 m long, and
(iii) is provided with doors having self-closing devices, or
(b) there is a second and separate egress doorway from each room or suite not leading into a dead-end corridor.
(12) A dead-end corridor is permitted in a high-hazard industrial occupancy where there is a second and separate egress
doorway from each room or suite not leading into a dead-end corridor.
(1) Except as otherwise required by this Section, aisles shall be provided in conformance with the Fire Code made under
the Fire Protection and Prevention Act, 1997.
(1) Except as permitted by Sentence (5) and Article 3.3.1.12., a door that opens into a corridor or other facility
providing access to exit from a suite or room not located within a suite, shall swing on a vertical axis.
(2) Except as permitted by Article 3.3.1.12., a door that opens into a corridor or other facility providing access to exit
from a room or suite shall swing in the direction of travel to the exit if the room or suite is used or intended for
(a) an occupant load more than 60,
(b) a high-hazard industrial occupancy, or
(c) a hazardous classroom in an elementary or secondary school.
(3) Every door that divides a corridor that is not wholly contained within a suite shall swing on a vertical axis in the
direction of travel to the exit where the corridor provides access to exit for
(a) an occupant load more than 60,
(b) a high-hazard industrial occupancy,
(c) a hazardous classroom in an elementary or secondary school,
(d) a Group B, Division 2 or 3 occupancy, or
(e) a retirement home.
(4) If a pair of doors is installed in a corridor that provides access to exit in both directions, the doors shall swing in
opposite directions, with the door on the right hand side swinging in the direction of travel to the exit.
(5) Doors that serve individual storage spaces not more than 28 m2 in area in self-service storage buildings need not
conform to Sentence (1).
3.3.1.12.Sliding Doors permalink →
(1) Except as permitted by Sentences (2) and 3.3.1.11.(5), a sliding door provided in the locations described in
Article 3.3.1.11. shall
(a) be designed and installed to swing on the vertical axis in the direction of travel to the exit when pressure is applied,
and
(b) be identified as a swinging door by means of a label or decal affixed to it.
(2) In a Group B, Division 1 occupancy, or in an impeded egress zone in other occupancies, sliding doors used in an
access to exit need not conform to Sentence (1) and Article 3.3.1.11.
(3) Movable partitions used to separate a public corridor from an adjacent business and personal services occupancy or
a mercantile occupancy need not conform to Sentence (1) and Sentences 3.3.1.11.(1) and (2) provided the partitions are
not located in the only means of egress. (See Note A-3.3.1.12.(3))
3.3.1.13.Doors and Door Hardware (See also Sentence 3.8.3.6.(17)) permalink →
(1) Except as required by Article 3.3.3.4. and Sentences 3.3.4.11.(11), 3.8.3.3.(1) and (2), a door that opens into or is
located within a public corridor or other facility that provides access to exit from a suite shall
(a) provide a clear opening of not less than 850 mm, if there is only one door leaf,
(b) in a doorway with multiple leaves, have the active leaf providing a clear opening of not less than 850 mm,
(c) not open onto a step, and
e1 (d) have a threshold not more than 13 mm higher than the floor surface, except where
(i) the threshold is used to contain spillage, or
(ii) the doorway provides access to an exterior balcony, other than a balcony required by Sentence 3.3.1.7.(2).
(2) Except as provided in Sentences (6) and (7), a door in an access to exit shall be readily openable in travelling to an
exit without requiring keys, special devices or specialized knowledge of the door opening mechanism.
(3) Except as permitted by Sentence (4), door release hardware shall be operable by one hand and the door shall be
openable with not more than one releasing operation. (See also Sentence 3.8.3.6.(4))
(4) Except in a retirement home, an egress door from an individual dwelling unit or from a suite of residential
occupancy is permitted to be provided with additional devices that require a releasing operation additional to the main
door release hardware, provided the devices are readily operable from the inside without the use of keys, special devices
or specialized knowledge. (See Note A-3.3.1.13.(4))
(5) Door release hardware shall be installed not more than 900 mm and 1 100 mm above the finished floor.
(6) An egress door in an access to exit serving a contained use area or an impeded egress zone is permitted to be
equipped with locking devices, provided they can be released either locally or remotely in conformance with Sentence (8)
or (9). (See Note A-3.3.1.13.(6))
(7) A door in an access to exit is permitted to be equipped with an electromagnetic locking device conforming to
Sentence 3.4.6.16.(5), except that this permission does not apply to a door
(a) in an elementary or secondary school,
(b) a door leading from a Group F, Division 1 occupancy, or
(c) except as provided in Sentence (11), requiring a latch release device by Article 3.3.2.6.
(8) Local locking devices permitted by Sentence (6) shall be operable by a key from both sides of the door.
(9) Controls for the remote release of door locking devices permitted by Sentence (6) shall be located in an area readily
available to security personnel.
(10) Locking devices permitted by Sentence (6) that are electrically operated shall be
(a) designed to operate on emergency power, and
(b) capable of manual release by security personnel.
(11) A door in an access to exit in a gaming premise is permitted to be equipped with an electromagnetic locking device
conforming to Sentences 3.4.6.16.(5) and (8).
3.3.1.14.Ramps and Stairways permalink →
(1) Except as permitted by Sentence (2), Article 3.3.4.7. and Subsection 3.3.2., ramps and stairways that do not serve as
exits shall conform to the requirements for exit ramps and stairways stated in Sentence 3.4.3.2.(8) and Articles 3.4.3.4.,
and 3.4.6.1. to 3.4.6.9.
(2) Ramps and stairways that serve service rooms, service spaces or industrial occupancies need not comply with
Sentence (1), provided
(a) they are intended only for occasional use for servicing equipment and machinery, and
(b) they do not serve as exits.
3.3.1.15.Exterior Passageways permalink →
(1) An exterior passageway leading to a required exit shall conform to the requirements of Section 3.4. for exterior exit
passageways.
3.3.1.16.Tapered Treads in a Curved Flight permalink →
(1) Flights of stairs shall consist solely of
(a) straight flights, or
(b) curved flights complying with Sentence (2).
(2) Tapered treads in a curved flight that is not required as an exit shall have
(a) a minimum run of 150 mm,
(b) a run not less than 280 mm when measured at a point 300 mm from the centre line of the handrail at the narrow end
of the tread, and
(c) a riser conforming to Sentence 3.4.6.8.(2).
(3) Tapered treads shall have a consistent angle and uniform run and rise dimensions in accordance with the
construction tolerances described in Article 3.4.6.8. when measured at a point 300 mm from the centre line of the handrail
at the narrow end of the tread.
(4) All tapered treads within a flight shall turn in the same direction.
3.3.1.17.Capacity of Access to Exits (See Article 3.3.1.9. for minimum widths of corridors.) permalink →
(1) The capacity of an access to exit shall be based on the occupant load of the portion of the floor area served.
(2) In an access to exit the required width of ramps with a slope not more than 1 in 8, doorways, and corridors shall be
based on not less than 6.1 mm per person.
(3) In an access to exit the required width of a ramp with a slope more than 1 in 8 shall be based on not less than
9.2 mm per person.
(4) In an access to exit from a floor area used or intended to be used for patients or residents in a Group B, Division 2
or Division 3 occupancy, the required width of corridors, doorways, and ramps shall be based on not less than 18.4 mm
per person.
(5) The capacity of stairs in an access to exit shall conform to the requirements for stairs in Sentences 3.4.3.2.(1) to (3).
(6) In a building that is not sprinklered throughout in accordance with Sentence 3.2.5.12.(1), an access to exit that is
part of the principal entrance serving a dance hall or a licensed beverage establishment with an occupant load more than
250 shall be at least one-half of the required exit width.
(1) Except as provided in Sentences (5) and (6) and Articles 3.3.2.9. and 3.3.4.7., a guard not less than 1 070 mm high
shall be provided
(a) around each roof to which access is provided for other than maintenance,
(b) at openings into smoke shafts referred to in Subsection 3.2.6. that are less than 1 070 mm above the floor, and
(c) at each raised floor, mezzanine, balcony, gallery, interior or exterior vehicular ramp, and at other locations where
(See Note A-9.8.8.1.)
(i) the difference in level is more than 600 mm between the walking surface and the adjacent surface, or
(ii) the adjacent surface within 1.2 m of the walking surface has a slope of more than 1 in 2, and
(d) except as provided in Sentence (6), around each skylight located in a portion of a roof that is intended to be
occupied.
(2) Except as provided in Sentences (3) and 3.3.2.9.(4), openings through any guard that is required by Sentence (1)
shall be of a size that will prevent the passage of a sphere having a diameter more than 100 mm unless it can be shown
that the location and size of openings that exceed this limit do not represent a hazard.
(2.1) Except as permitted by Sentence 3.3.5.10.(1), openings through any guard that is required by Sentence (1) and that
is installed in a building of industrial occupancy shall be of a size which will prevent the passage of a sphere having a
diameter more than 200 mm unless it can be shown that the location and size of openings that exceed this limit do not
represent a hazard.
(3) Openings through any guard that is not required by Sentence (1) and that serves a building of other than industrial
occupancy, shall be of a size that
(a) will prevent the passage of a sphere having a diameter more than 100 mm, or
(b) will permit the passage of a sphere having a diameter more than 200 mm unless it can be shown that the location and
size of openings that exceed these limits do not represent a hazard.
(See Note A-9.8.8.5.(4))
(4) Unless it can be shown that the location and size of openings do not present a hazard, a guard shall be designed so
that no member, attachment or opening located between 140 mm and 900 mm above the level protected by the guard will
facilitate climbing.
(5) Sentence (1) does not apply
(a) to the front edges of stages,
(b) to loading docks,
(c) to floor pits in repair garages, or
(d) where access is provided for maintenance purposes only.
(6) Clause (1)(d) does not apply to a skylight that
(a) is designed to support the loads specified in Part 4, or
(b) is provided with a skylight screen that
(i) has openings not more than 100 mm wide, and
(ii) can resist a concentrated load of 1.3 kN applied perpendicular at any point on the screen, without the
deflection from this loading resulting in the breakage of the skylight glazing.
3.3.1.19.Tactile Walking Surface Indicators permalink →
(1) Except as provided in Sentence (2), tactile attention indicators conforming to Article 3.8.3.18., shall be installed
(a) at the top of flights of stairs that are unenclosed, and
(b) at drop-off edges with a change in elevation greater than 300 mm that are unprotected by a guard.
(See Note A-3.3.1.19.(1))
(2) Sentence (1) does not apply to service spaces, bleachers addressed in Subsection 3.3.2., stages, loading docks,
industrial occupancies, within dwelling units, and to stairs and drop-off edges serving not more than two dwelling units.
3.3.1.20.Transparent Doors and Panels permalink →
(1) Except for dwelling units and as permitted by Sentence (5), a glass or transparent door shall be designed and
constructed so that the existence and position of the door is readily apparent, by attaching visually contrasting hardware,
bars or other permanent fixtures to it.
(2) Fully glazed transparent doors, and fully glazed transparent sidelights and panels with widths greater than 300 mm,
shall be marked in conformance with Sentence 3.8.3.3.(15).
(3) A glass door shall be constructed of
(a) laminated or tempered safety glazing conforming to CAN/CGSB-12.1, “Safety Glazing,” or
(b) wired glass conforming to CAN/CGSB-12.11-M, “Wired Safety Glass.”
(4) Except as permitted by Sentence (5), transparent panels used in an access to exit that, because of their physical
configuration or design, could be mistaken as a means of egress shall be made inaccessible by barriers or railings.
(5) Sliding glass partitions that separate a public corridor from an adjacent occupancy and that are open during normal
working hours need not conform to Sentences (1) and (4), provided the partitions are suitably marked in conformance
with Sentence (2) to indicate their existence and position.
(6) Glass in a vision panel in a door or in a transparent sidelight shall conform to Sentence 3.8.3.3.(14).
(7) Glass in doors and glass sidelights that could be mistaken for doors, within or at the entrances to dwelling units and
in public areas, shall conform to the requirements of Article 9.6.1.4.
(8) A window in a public area that extends to less than 1 000 mm above the floor and is located above the second storey
in a building of residential occupancy, shall be protected by a barrier or railing from the floor to not less than 1 070 mm
above the floor, or the window shall be non-openable and designed to withstand the lateral design loads for balcony
guards required by Article 4.1.5.14.
3.3.1.21.Exhaust Ventilation and Explosion Venting permalink →
(1) Except as provided in Sentence (2), an exhaust ventilation system designed in conformance with the appropriate
requirements of Part 6 shall be provided in a building or part of a building in which dust, fumes, gases, vapour or other
impurities or contaminants have the potential to create a fire or explosion hazard. (See also Article 4.2.4.13.)
(2) Where a fire separation required to have a fire-resistance rating is penetrated by a ventilation system required by
Sentence (1) for power-ventilated enclosures in laboratories, the ducts shall be
(a) continuously enclosed from the first penetrated fire separation to any subsequent fire separations or concealed
spaces and all the way through to the outdoors so that the highest fire-resistance rating of all the penetrated fire
separations is maintained, and
(b) exempted from the requirement to be equipped with a fire damper, smoke damper and combination smoke/fire
damper as stated in Article 3.1.8.7.
(3) Explosion relief devices, vents or other protective measures conforming to Subsection 6.3.1. and Article 6.9.1.2.
shall be provided for a space in which substances or conditions that have the potential to create an explosion hazard are
present as a result of the principal use of a building.
3.3.1.22.Janitors’ Rooms permalink →
(1) Except as permitted by Sentences (2) and (3), a room or space within a floor area for the storage of janitorial
supplies shall be separated from the remainder of the building by a fire separation having a fire-resistance rating not less
than 1 h.
(2) The fire-resistance rating of the fire separation required by Sentence (1) is permitted to be less than 1 h but not less
than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for
(a) the floor assembly above the floor area, or
(b) the floor assembly below the floor area, if there is no floor assembly above.
(3) The fire separation required by Sentence (1) is not required to have a fire-resistance rating if the floor area in which
the room or space is located is sprinklered throughout.
3.3.1.23.Common Laundry Rooms permalink →
(1) Except as permitted by Sentences (2) and (3), in a building of residential occupancy, a laundry room in a floor area
that is not within a dwelling unit shall be separated from the remainder of the building by a fire separation having a fire-
resistance rating not less than 1 h.
(2) The fire-resistance rating of the fire separation required by Sentence (1) is permitted to be less than 1 h but not less
than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for
(a) the floor assembly above the floor area, or
(b) the floor assembly below the floor area, if there is no floor assembly above.
(3) The fire separation required by Sentence (1) is not required to have a fire-resistance rating if the floor area in which
the laundry room is located is sprinklered throughout.
(1) No obstruction shall be permitted in any occupancy that would restrict the width of a normal means of egress from
any part of a floor area to less than 750 mm unless an alternative means of egress is provided adjacent to, accessible
from, and plainly visible from the obstructed means of egress. (See Note A-3.3.1.24.(1))
3.3.1.25.Signs in Service Spaces permalink →
(1) Illuminated signs conforming to Sentence 3.4.5.1.(2) and (6) shall be provided to indicate the direction to egress
points in a service space referred to in Sentence 3.2.1.1.(8).
3.3.1.26.Welding and Cutting permalink →
(1) Except as provided in Sentence (2), welding and cutting operations shall be carried out in a room
(a) separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h, or
(b) protected by an automatic fire extinguishing system.
(2) Sentence (1) shall not apply to industrial occupancies where the welding and cutting operations do not present a fire
or explosion hazard to adjacent areas.
3.3.2.Assembly Occupancy
(1) This Subsection applies to assembly occupancies and to outdoor places of assembly.
3.3.2.2.Fire Separations permalink →
(1) Except as permitted by Sentence (2), the seating area of a Group A, Division 1 occupancy shall be separated from
adjacent occupancies in the floor area by a fire separation having a fire-resistance rating not less than 1 h if the occupant
load in the seating area exceeds 200.
(2) The fire-resistance rating of the fire separation required by Sentence (1) is permitted to be less than 1 h but not less
than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for
(a) the floor assembly above the floor area, or
(b) the floor assembly below the floor area, if there is no floor assembly above.
(3) If usable space exists under tiers of seats in arena-type buildings, a fire separation with a fire-resistance rating not
less than 45 min shall be provided between the space and the seats or the space shall be sprinklered.
(4) Except as required in Sentences (5) to (7), in an elementary or secondary school, a hazardous classroom shall be
separated from the remainder of the building by a fire-separation having a fire-resistance rating not less than
(a) 1 h where the building is not sprinklered, or
(b) 30 min where the building is sprinklered throughout.
(5) Except as provided in Sentence (6), in an elementary or secondary school, a hazardous classroom containing an auto
repair shop shall be separated from the remainder of the building by a fire-separation having a fire-resistance rating not
less than
(a) 2 h where the building is not sprinklered, or
(b) 1 h where the building is sprinklered throughout.
(6) In an elementary or secondary school, if there is a group of hazardous classrooms or a group of hazardous
classrooms and ancillary rooms of a complementary use, the fire separation required by Sentence (4) or (5) need not be
provided within the group but the fire separation is required between the group and the remainder of the building.
(7) In an elementary or secondary school, a hazardous classroom containing a spray painting operation shall be
separated from the remainder of the building by a fire separation having a fire-resistance rating not less than
(a) 2 h, or
(b) 1 h where the spray painting operation is separated from the classroom by a fire-separation having a fire-resistance
rating not less than 1 h.
(8) Except as required in Sentence (9), in an elementary or secondary school, where the occupant load of a room
exceeds 200 persons, the room and any ancillary rooms of a complementary use shall be separated from the remainder of
the building by a fire separation having a fire-resistance rating not less than
(a) 1 h where the building is not sprinklered, or
(b) 30 min where the building is sprinklered throughout.
(9) A kitchen shall not be located within the fire compartment required in Sentence (8).
3.3.2.3.Reserved
(1) Except for the requirements of Article 3.3.2.8. for bench-type seats and except as required or permitted by
Sentence (2) and Articles 3.3.2.11. and 3.3.2.12., fixed seats in places of assembly shall be
(a) attached or secured to the floor, platform or platform riser,
(b) provided with arms and back, and
(c) arranged in rows having an unobstructed passage not less than 400 mm wide measured horizontally between plumb
lines from the backs of the seats in one row and the edges of the furthest forward projection of the seats in the next
row in the unoccupied position.
(2) For fixed seats with backs and with folding tablet arms, the value of 400 mm required by Clause (1)(c) shall be
measured when the tablet arms are in the use position, but is permitted to be measured in the stored position provided
(a) there are not more than 7 seats between any seat and the nearest aisle,
(b) the seats are located in a lecture hall or an auditorium used for instructional purposes, and
(c) the tablet arm, when raised manually to a vertical position, falls by the force of gravity to the stored position.
(See Note A-3.3.2.4.(2))
(3) Except as permitted by Sentences (4) and (5), aisles shall be located so that there are not more than 7 seats with
backs or 20 seats without backs between any seat and the nearest aisle.
(4) The requirements of Sentence (3) do not apply if
(a) egress doorways are provided to serve both ends of rows of seats,
(b) each doorway referred to in Clause (a) serves not more than 3 rows of seats, and
(c) each row contains not more than 100 seats.
(5) The requirements of Sentence (3) do not apply if
(a) there are not more than 7 seats between any seat and the nearest aisle, where the seats are served by a single aisle,
(b) there are not more than 20 seats between any seat and the nearest aisle, where the seats are served by two aisles,
(c) each row has an unobstructed passage with minimum width of 400 mm plus 6.1 mm for each additional seat above
16 seats in the row, and
(d) the travel distance is not more than 45 m measured along the path of travel from any seat to an exit or to an egress
doorway.
(6) Seating arrangements that do not conform to the requirements of Sentences (3) to (5) are permitted provided the
standard of safety is not reduced and the time required for egress is not increased.
(1) Except as required by Articles, 3.3.2.11. and 3.3.2.12., aisles leading to egress doors or exits shall be provided in
conformance with Sentences (2) to (27) in places of assembly that contain fixed seats.
(2) In this Subsection, a converging aisle is an aisle into which the occupants of two or more aisles converge in
travelling to an exit.
(3) An aisle shall terminate at
(a) a converging aisle,
(b) an egress doorway from the seating area, or
(c) an exit from the seating area.
(4) A converging aisle shall terminate at
(a) an egress doorway from the seating area, or
(b) an exit from the seating area.
(5) The minimum clear width of aisles shall be not less than 1 100 mm, except that the width is permitted to be reduced
to not less than
(a) 750 mm if serving not more than 60 seats, and
(b) 900 mm if serving seats on one side only.
(6) The minimum clear width of each aisle shall be measured at the point in the aisle furthest from
(a) an egress doorway referred to in Clause (15)(a),
(b) an exit referred to in Clause (15)(b), or
(c) an exit referred to in Sentence (16).
(7) Except for an aisle serving bleacher seats, where rows of seats discharge into an aisle, the minimum clear width
required by Sentence (5) shall be increased by 25 mm for each metre of length of the aisle measured in the direction
towards an exit.
(8) The width of a converging aisle shall be not less than the required width of the widest aisle plus 50% of the total
required width of the remaining aisles that it serves.
(9) If rows of seats discharge directly into the converging aisle, the width required by Sentence (8) shall be increased by
25 mm for each metre of length of the aisle where the rows of seats discharge into the aisle.
(10) The width of an egress doorway or an exit leading directly from the seating area shall be not less than the required
width of the widest aisle or converging aisle plus 50% of the total required width of the remaining aisles and converging
aisles that it serves.
(11) The requirements in Sentences (5) to (10) and (17) do not apply if
(a) the minimum clear width of an aisle is in accordance with Article 3.3.1.17., but is not less than 900 mm if serving
seats on one side only,
(b) the minimum clear width of an aisle is in accordance with Article 3.3.1.17., but is not less than 1 200 mm if serving
seats on both sides,
(c) the minimum clear width of a converging aisle is in accordance with Article 3.3.1.17., but not less than the width of
the widest aisle leading to the converging aisle,
(d) the minimum clear width of an exit leading directly from the seating area is in accordance with Article 3.4.3.2.,
(e) except as provided in Clause (f), the minimum clear width of an egress doorway leading directly from the seating
area is in accordance with Article 3.3.1.17., but not less than the required width of the aisle or the converging aisle
leading to the doorway, and
(f) if more than one vomitory is provided
(i) the minimum total clear width of the egress doorways leading from one vomitory is not less than the required
width of the aisle or the converging aisle leading to the doorways, and
(ii) the minimum clear width of egress doorways from additional vomitories is in accordance with Article
3.3.1.17.
(12) Except as provided in Sentences (13) and (14), dead-end aisles shall be not more than 6 m long.
(13) Dead-end aisles are permitted to be more than 6 m long, but not more than 10 m long if
(a) the seating area is separated from other seating areas and adjacent occupancies, including a corridor serving any
seating area, by a fire separation in accordance with Sentences 3.3.2.2.(1) and (2),
(b) the travel distance is not more than 25 m measured along the path of travel from any seat to an exit, to an egress
doorway or to an opening into a vomitory,
(c) at least one means of egress, comprising not less than 30 percent of the required exit capacity, is through an exterior
exit, an exit stairway or a corridor not containing an occupancy,
(d) each row served by the dead-end aisle has a minimum unobstructed width of 400 mm plus 6.1 mm for each
additional seat above seven seats in a row, but not more than 550 mm,
(e) the minimum ceiling height above the seating area is 3 m,
(f) the activation of a fire detector or a sprinkler head in the seating area will
(i) cause the shutdown of the projection system serving the seating area, and
(ii) turn on the normal lighting in the seating area, and
(g) the floor area is sprinklered.
(14) Dead-end aisles are permitted to be more than 10 m long, but not more than 13 m long if
(a) the seating area is separated from other seating areas and adjacent occupancies, including a corridor serving any
seating area, by a fire separation in accordance with Sentences 3.3.2.2.(1) and (2),
(b) the travel distance is not more than 25 m measured along the path of travel from any seat to an exit, to an egress
doorway or to an opening into a vomitory,
(c) at least one means of egress, comprising not less than 30 percent of the required exit capacity, is through an exterior
exit, an exit stairway or a corridor not containing an occupancy,
(d) each row served by a dead-end aisle has a minimum unobstructed width of 400 mm plus 6.1 mm for each additional
seat above seven seats in a row, but not more than 550 mm,
(e) the activation of a fire detector or a sprinkler head in the seating area will
(i) cause the shutdown of the projection system serving the seating area, and
(ii) turn on the normal lighting in the seating area,
(f) a voice communication system is installed in conformance with Article 3.2.4.22.,
(g) a smoke control system is installed to control movement of smoke in the seating area or a smoke exhaust system is
provided so that, in the event of detection of smoke by a smoke detector in the seating area, air handling equipment
is activated to extract air directly from the seating area at the rate of at least six air changes per hour, and
(h) the floor area is sprinklered.
(15) Where a seating area is separated as required by Sentences 3.3.2.2.(1) and (2) or 3.3.2.2.(8), the length of travel by
any aisle shall be not more than 45 m measured from the most remote point of the aisle to
(a) an egress doorway in the required separation, or
(b) an exit leading directly from the seating area.
(16) Where a seating area is not required to be separated by Sentences 3.3.2.2.(1) and (2) or 3.3.2.2.(8), the travel
distance shall be not more than 45 m measured from the most remote point of the aisle to an exit.
(17) Side aisles shall be not less than 1 100 mm wide if seating is provided in conformance with Sentence 3.3.2.3.(4).
(18) An aisle that has a slope not more than 1 in 8 shall not be stepped.
(19) An aisle that slopes more than 1 in 8 shall be stepped.
(20) The passageway between rows of seats served by a stepped aisle shall be level at right angles to the line of travel.
(21) The riser of a step in an aisle shall be
(a) not less than 110 mm high, and
(b) not more than 200 mm high.
(22) Variations are permitted in riser height provided
(a) the height of adjacent risers does not vary by more than 6 mm, and
(b) the depth of a tread or a platform in the direction of travel is not less than 430 mm.
(23) Steps in an aisle shall
(a) have a run not less than 230 mm exclusive of nosings,
(b) have a tread depth not less than 250 mm,
(c) extend to the adjacent rows of seats in a manner that will not create a hazard from tripping, and
(d) have a finish on the treads conforming to Sentence 3.4.6.1.(1).
(24) The location of every riser in an aisle shall be made apparent from both directions of travel by strategically placed
lighting or contrasting marking stripes.
(25) A platform in an aisle shall be level, except that a slope not more than 1 in 50 is permitted for a platform that is not
less than 430 mm deep in the direction of exit travel.
(26) If a step is used at the entry to a row of seats from a stepped aisle, an unobstructed platform not less than 800 mm
square shall be provided adjacent to the aisle.
(27) The finish of the surface of a platform in or adjacent to a stepped aisle shall conform to Sentence 3.4.6.1.(1).
(1) Except as permitted by Sentences (2) to (4), a corridor used by the public in an assembly occupancy as an access to
exit shall be separated from the remainder of the floor area by a fire separation having a fire-resistance rating not less
than 1 h.
(2) The fire-resistance rating of the fire separation required by Sentence (1) is permitted to be less than 1 h but not less
than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for
(a) the floor assembly above the floor area, or
(b) the floor assembly below the floor area, if there is no floor assembly above.
(3) The fire-resistance rating required by Sentence (1) is permitted to be waived if the floor area in which the corridor
is located is sprinklered throughout.
(4) The requirement for a fire separation stated in Sentence (1) is permitted to be waived if the distance from any point
in the floor area to an exit measured along the path of travel to the exit does not exceed the travel distance permitted by
Article 3.4.2.5.
(1) A door equipped with a latching mechanism in an access to exit from a room or suite of assembly occupancy
containing an occupant load more than 100 shall be equipped with a device that complies with Sentence 3.4.6.16.(3).
3.3.2.8.Fixed Bench-Type Seats Without Arms permalink →
(1) If fixed bench-type seats without arms are provided, the seat width per person shall be assumed to be 450 mm.
(2) The centre-to-centre spacing between rows of bench-type seats shall be not less than 760 mm if back rests are
provided, and not less than 550 mm if back rests are not provided.
(3) A clear space of not less than 300 mm shall be provided between the back of each seat and the front of the seat
immediately behind it.
(1) Except as required by Sentences (2) to (4) for bleacher seats, guards shall be installed in outdoor and indoor places
of assembly with fixed seats so that
(a) at the fascia of every box, balcony or gallery where the seats extend to the edge, the height of guards is not less than
(i) 760 mm in front of the seats, and
(ii) 920 mm if located at the end of aisles or at the foot of steps,
(b) the height of guards along every cross aisle other than those adjacent to the fascia of every box, balcony or gallery is
not less than 660 mm, except that guards need not be provided if the backs of the seats along the front side of the
aisle are not less than 600 mm above the floor of the aisle, and
(c) where the seating is arranged in successive tiers and the height of rise between platforms is more than 450 mm, the
height of guards is not less than 660 mm along the entire row of seats at the edge of the platform.
(2) The backs and ends of bleacher seats more than 1 200 mm above the ground or floor that are not adjacent to a wall
shall be protected with a guard
(a) not less than 1 070 mm high above an adjacent aisle surface or foot rest, and
(b) not less than 920 mm high above the centre of an adjacent seat board.
(3) If the front of a bleacher is more than 600 mm above the ground or floor, it shall be protected with a guard not less
than 840 mm high above the front foot rest.
(4) The size of any opening in a guard required by Sentences (2) and (3) shall not allow the passage of a sphere whose
diameter is more than 300 mm.
3.3.2.10.Handrails in Aisles with Steps (See Note A-3.3.2.10.) permalink →
(1) Handrails shall be provided in aisles with steps in conformance with Table 3.3.2.10.
(2) Handrails installed along aisle centre lines as required by Table 3.3.2.10. shall
(a) comply with Sentences 3.4.6.5.(5) to (7) and (14),
(b) have gaps not less than 560 mm and not more than 915 mm wide, measured horizontally, at intervals not exceeding
five rows,
(c) comply with Sentence 3.4.6.5.(11) at terminations and required gaps, and
(d) have an intermediate rail located 305 mm below the principal handrail.
Table 3.3.2.10.
Types and Location of Handrails in Aisles with Steps
Forming Part of Sentences 3.3.2.10.(1) and (2)
Aisle Serving Seating on One Side Aisle Serving Seating on Both Sides
Aisle Width
Handrail Requirements
A continuous handrail located on the side of the aisle A handrail located on one side at the end of each row
Less than 1 100 mm opposite the seats that conforms to Sentences of seats that conforms to Sentences 3.4.6.5.(5) to (8),
3.4.6.5.(5) to (8), (11), (13) and (14). (11), (13) and (14).
A centre line handrail that conforms to Sentence (2), or
A continuous handrail located on the side of the aisle
1 100 mm or more opposite the seats that conforms to Sentences A centre line handrail that conforms to Sentence (2).
3.4.6.5.(5) to (8), (11), (13) and (14), plus a handrail
located at the end of each row of seats that conforms
to Sentences 3.4.6.5.(5) to (8), (11), (13) and (14).
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
3.3.2.11.Outdoor Places of Assembly permalink →
(1) A Group A, Division 4 occupancy and each tier or balcony that has a capacity of more than
(a) 1 000 persons shall have no fewer than three separate exits, or
(b) 4 000 persons shall have no fewer than four separate exits.
(2) In a Group A, Division 4 occupancy, every seat shall be located so that the travel distance is not more than 45 m
measured along the path of travel from the seat to
(a) the ground,
(b) an exit,
(c) an opening to a passageway leading from the seating area, or
(d) a portal, a vomitory or any other opening through the seating deck structure.
(3) Exits from outdoor stadia or grandstands shall be located not more than 25 m apart.
(4) The capacity of a means of egress for a Group A, Division 4 occupancy shall conform to the requirements of
Sentence 3.4.3.2.(3).
(5) Aisles in a Group A, Division 4 occupancy shall
(a) be located so that there are not more than 20 seats between any seat and the nearest aisle, and
(b) be not less than 1 200 mm wide, except that an aisle serving less than 60 persons is permitted to be 750 mm wide.
(1) Steps provided in aisles of bleachers of the telescopic type shall
(a) have risers not more than 250 mm high, and
(b) have treads with a run not less than 280 mm.
(2) If the vertical distance between seating platforms in bleachers is more than 280 mm, an intermediate step shall be
provided the full width of the aisle and proportioned to provide 2 equal risers between platforms.
(3) If the vertical distance between seating platforms in bleachers is more than 450 mm, 2 intermediate steps shall be
provided the full width of the aisle so that there are 3 equal risers between platforms.
(4) If the passageway between rows of seats is not a closed deck, footboards shall be provided so that
(a) the total width of the footboards shall be not less than three-quarters of the centre-to-centre spacing between rows of
seats, and
(b) the spacing between footboard members shall be not more than 25 mm.
(5) Openings above footboards and below the seats in rows of bleacher seats shall be provided with intermediate
construction so that there is no opening that would permit the passage of a sphere of more than 100 mm in diameter.
(1) Except as permitted by Sentence (2), a library book storage room that is not normally accessible to the public shall
be separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 2 h if it
(a) is more than 250 m2 in area, or
(b) contains book stacks that
(i) are more than 10 m high, or
(ii) penetrate more than one floor assembly.
(2) The fire separation required by Sentence (1) is not required if the book storage room is sprinklered.
(3) Open book shelves are permitted above and below a mezzanine floor in a library building provided the height of the
shelves is not more than 2.1 m but not more than 75% of the floor-to-ceiling height of the space above or below the
mezzanine floor assembly.
3.3.2.14.Stages for Theatrical Performances permalink →
(1) A stage for theatrical performances and ancillary spaces, including workshops, dressing rooms and storage areas,
shall be sprinklered.
(2) A fire separation with a fire-resistance rating not less than 1 h shall be provided between a stage for theatrical
performances and ancillary spaces, including workshops, dressing rooms and storage areas.
(3) Except as permitted by Sentence (6), a stage for theatrical performances and ancillary spaces, including workshops,
dressing rooms and storage areas, shall be separated from the seating area by a fire separation having a fire-resistance
rating not less than 1 h, except for a proscenium opening protected with
(a) a sprinkler deluge system conforming to the requirements of NFPA 13 “Standard for the Installation of Sprinkler
Systems,”
(b) an unframed fire curtain if the opening is not more than 20 m wide, or
(c) a semi-rigid fire curtain if the opening is more than 20 m wide.
(4) A fire curtain required by Sentence (3) shall be of a type acceptable to the principal authority and designed to close
(a) automatically upon the actuation of the sprinkler system,
(b) automatically upon actuation of the fire alarm system, and
(c) manually by remote control devices located at the curtain control panel and at each side of the stage.
(5) At least 2 vents for the purpose of venting fire and smoke to the outside of a building shall be provided above a
stage designed for theatrical performances and shall
(a) have an aggregate area not less than one-eighth of the area of the stage behind the proscenium opening, and
(b) be arranged to open automatically upon actuation of the sprinkler system.
(6) The fire separation referred to in Sentence (3) is not required between a stage and a seating area in a floor area that
is sprinklered, provided a sprinkler deluge system is installed at the boundary between the stage and the seating area.
3.3.2.15.Risers for Stairs permalink →
(1) In a Group A, Division 2 occupancy used for the serving of food and beverages, an interior flight of stairs with fewer
than 3 risers is permitted provided it
(a) is not less than 900 mm wide,
(b) is illuminated at all times that occupants are on the premises, and
(c) has a handrail on each side.
3.3.2.16.Storage Rooms permalink →
(1) A room intended for the storage of flammable liquids or combustible liquids required by the Fire Code made under
the Fire Protection and Prevention Act, 1997 shall not be located above or below the first storey of the building.
3.3.2.17.Safety Glazing permalink →
(1) Except as permitted in Sentence (3), glazing in all fixed and operable panels of doors shall conform to Class A of
CAN/CGSB-12.1, “Safety Glazing.”
(2) Except as permitted in Sentence (4), glazing in all fixed and operable panels of windows shall conform to Class A of
CAN/CGSB-12.1, “Safety Glazing.”
(3) Glazing in individual fixed or operable panels of a door need not comply with Sentence (1), where
(a) the bottom exposed edge of the glazing is located more than 1 525 mm above the walking surface on each side of
the door, or
(b) the glazed opening in the door does not permit the passage of a sphere whose diameter is more than 75 mm.
(4) Glazing in individual fixed or operable panels of a window need not comply with Sentence (2), where
(a) the bottom exposed edge of the glazing is located more than 1 525 mm above the walking surface on each side of
the window, or
(b) the glazing is located more than 915 mm away from the walking surface on each side of the window measured
perpendicular to the plane of the glazing.
3.3.3.Care, Care and Treatment or Detention Occupancy
(1) This Subsection applies to care occupancies, care and treatment occupancies and detention occupancies. (See Note
A-3.3.3.1.(1))
3.3.3.2.Fire Separations permalink →
(1) The fire separation required by Sentence 3.3.5.5.(1) between a care, care and treatment or detention occupancy and
a repair garage shall have no openings.
(2) Except as permitted by Sentence (4), in a Group B, Division 3 occupancy, walls between sleeping rooms and
adjacent rooms shall be constructed as fire separations having a fire-resistance rating not less than 1 h, except that the
fire-resistance rating need not be more than 45 min where the floor assembly is not required to be more than 45 min.
(3) Except as permitted by Sentence (4), in a Group B, Division 3 occupancy, walls separating corridors serving
sleeping rooms from adjacent rooms shall be constructed as fire separations having a fire-resistance rating not less than
1 h, except that the fire-resistance rating need not be more than 45 min where the floor assembly is not required to be
more than 45 min.
(4) The walls separating sleeping rooms from adjacent rooms and corridors in those parts of a floor area classified as a
Group B, Division 3 occupancy shall be constructed as fire separations but are not required to have a fire-resistance
rating if
(a) those parts of the floor area contain sleeping accommodation for not more than 10 persons, and
(b) not more than 6 occupants require assistance in evacuation in case of an emergency.
(5) The door in the fire-separation required in Sentence (4) is permitted to be equipped with a roller latch and need not
be provided with a self-closing device.
(1) A corridor used by the public or serving patients or residents shall have no dead-end portion unless the area served
by the dead-end portion has a second and separate means of egress.
(2) A corridor serving patients in a hospital shall be not less than 2 400 mm wide.
(3) Except as permitted in Sentence (5), a corridor serving residents who are not ambulatory in a Group B, Division 2 or
3 occupancy shall be not less than 1 650 mm wide.
(4) Paired doors in a corridor serving patients or residents shall
(a) swing in opposite directions, the right hand door swinging in the direction of travel, and
(b) be not less than 1 100 mm wide.
(5) A corridor in a Group B, Division 3 occupancy that contains sleeping accommodation for not more than 10 persons
and not more than 6 occupants require assistance in evacuation in case of an emergency need not comply with
Sentence (3).
(1) In a Group B, Division 2 or 3 occupancy, the minimum clear width of doorways through which it is necessary to
move a patient or resident in a bed shall be 1 050 mm. (See Note A-3.3.3.4.(1))
3.3.3.5.Hospitals and Long-Term Care Homes permalink →
(1) Floor areas containing patients’ or residents’ sleeping rooms in a hospital or long-term care home shall conform to
Sentences (2) to (12). (See Note 3.3.3.5.(1))
(2) Except as permitted by Sentence (3), a floor area containing patients’ or residents’ sleeping rooms in a hospital or
long-term care home shall be divided into no fewer than two fire compartments, each not more than 1 000 m2 in area.
(3) The floor area on either side of a horizontal exit conforming to Article 3.4.6.10. is permitted to be considered as a
fire compartment in applying the requirements of this Article.
(4) Except as permitted by Sentence (5), fire separations separating fire compartments required by Sentence (2) shall
have a fire-resistance rating not less than 1 h.
(5) The fire-resistance rating of a fire separation referred to in Sentence (4) is permitted to be less than 1 h but not less
than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for
(a) the floor assembly above the floor area, or
(b) the floor assembly below the floor area, if there is no floor assembly above.
(6) Reserved.
(7) The travel distance from any point within each fire compartment referred to in Sentence (2) to a door to an adjoining
fire compartment shall be not more than 45 m.
(8) Each fire compartment referred to in Sentence (2) shall be capable of accommodating, in addition to its own
occupants, the occupants of the largest adjacent fire compartment based on a clear floor space of 2.5 m 2 per patient or
resident in the adjacent fire compartment.
(9) Except as permitted by Sentences (10) and (11), walls between patients’ or residents’ sleeping rooms and the
remainder of the floor area shall be constructed as fire separations but are not required to have a fire-resistance rating
unless a fire-resistance rating is required by other provisions in this Part.
(10) The fire separation requirements of Sentence (9) do not apply to walls within a group of intercommunicating
patients’ or residents’ rooms, provided the group of rooms does not
(a) contain more than 5 patients or residents, or
(b) include storage, bathing or toilet facilities serving persons not occupying the group of rooms.
(See Note A-3.3.3.5.(10))
(11) A door in a fire separation required by Sentence (9) is permitted to be equipped with a roller latch.
(12) A fire separation required by Sentence (9) shall not contain any grilles, louvres or other openings.
3.3.3.6.Protection for Special Care and Treatment Facilities permalink →
(1) Compartments containing rooms such as operating rooms, recovery rooms, delivery rooms, intensive care units and
critical care units, from which it is impracticable to move patients in an emergency, shall be
(a) separated from adjacent spaces by fire separations having a fire-resistance rating not less than 1 h, and
(b) provided with a mechanical air supply so that during a period of 2 h after the start of a fire in another space, the
compartments will not contain more than 1% by volume of contaminated air from the fire area.
3.3.3.7.Contained Use Areas permalink →
(1) A contained use area shall conform to Sentences (2) to (5).
(2) A contained use area shall be separated from the remainder of the building by a fire separation having a fire-
resistance rating not less than 1 h.
(3) Except as permitted by Sentence (4), a building that includes a contained use area shall be sprinklered throughout.
r1 (4) A contained use area, in a building for which Articles 3.2.2.20. to 3.2.2.93. do not require the installation of an
automatic sprinkler system, is not required to be sprinklered as required by Sentence (3) provided
(a) the building is designed so that during a period of 2 h after the start of a fire in the contained use area, other fire
compartments will not contain more than 1% by volume of contaminated air from the contained use area,
(b) the building is designed so that during a period of 2 h after the start of a fire in another part of the building, the
contained use area will not contain more than 1% by volume of contaminated air from the other part of the building,
(c) all doors are designed to be remotely released in conformance with Sentence 3.3.1.13.(6), and
(d) the contained use area does not contain any rooms lined with combustible padding.
(5) A corridor serving a contained use area shall have no dead-end portion unless the area served by the dead-end
portion has a second and separate means of egress.
(1) Corridors and ramps used by residents in a long-term care home shall be equipped with handrails on each side
conforming to Sentences 3.4.6.5.(5) to (7) and (11) to (13).
3.3.4.Residential Occupancy
(1) This Subsection applies to residential occupancies.
3.3.4.2.Fire Separations permalink →
(1) Except as permitted by Sentences (2) and 3.2.2.9.(2), suites of residential occupancy shall be separated from each
other and the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h.
(2) The fire-resistance rating of the fire separation required by Sentence (1) is permitted to be less than 1 h but not less
than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for
(a) the floor assembly above the floor area, or
(b) the floor assembly below the floor area, if there is no floor assembly above.
(3) Floor assemblies within a dwelling unit need not be constructed as fire separations provided
(a) the distance between the lowest floor level and the uppermost floor level within the dwelling unit is not more than
6 m, and
(b) the dwelling unit is separated from the remainder of the building by a fire separation having a fire-resistance rating
not less than
(i) 1 h if the building is not sprinklered throughout,
(ii) 45 min if the building is sprinklered throughout and it is not more than 3 storeys in building height, or
(iii) 1 h if the building is sprinklered throughout and it is more than 3 storeys in building height.
(4) Except in a retirement home, the fire-resistance rating of the fire separation located between a dwelling unit and an
attached storage garage need not conform to that required by Sentence 3.3.5.6.(1) provided
(0.a) the storage garage contains not more than five vehicles,
(a) the dwelling unit and the attached storage garage are sprinklered,
(b) the dwelling unit is separated from the remainder of the building in conformance with Sentences (1) to (3),
(c) there are no air duct systems connecting the storage garage and the dwelling unit,
(d) the construction between the storage garage and the dwelling unit provides an effective barrier to gas and exhaust
fumes, and
(e) every door between the storage garage and the dwelling unit is
(i) tight fitting and weather-stripped to provide an effective barrier against the passage of gas and exhaust fumes,
(ii) fitted with a self-closing device, and
(iii) not located in a room intended for sleeping.
(5) Except in a retirement home, the fire separation required by Sentence 3.3.5.6.(1) is not required between a dwelling
unit and an attached storage garage, serving that dwelling unit only, provided
(a) the dwelling unit and its attached storage garage are separated from the remainder of the building in conformance
with Sentences (1) to (3),
(b) there are no air duct systems connecting the storage garage and the dwelling unit,
(c) the construction between the storage garage and the dwelling unit provides an effective barrier to gas and exhaust
fumes, and
(d) every door between the storage garage and the dwelling unit is
(i) tight fitting and weather-stripped to provide an effective barrier against the passage of gas and exhaust fumes,
(ii) fitted with a self-closing device, and
(iii) not located in a room intended for sleeping.
(1) Sprinklers shall be installed in a storage room provided for the use of tenants in a residential occupancy within a
floor area but not contained within a suite.
(2) Except as permitted by Sentence (3), a storage room referred to in Sentence (1) shall be separated from the
remainder of the building by a fire separation having a fire-resistance rating not less than 1 h.
(3) The fire-resistance rating of the fire separation required by Sentence (2) is permitted to be less than 1 h but not less
than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for
(a) the floor assembly above the floor area, or
(b) the floor assembly below the floor area, if there is no floor assembly above.
(4) Except where located within a dwelling unit, a room intended for the storage of flammable liquids or combustible
liquids required by the Fire Code made under the Fire Protection and Prevention Act, 1997 shall not be located above or
below the first storey of the building.
3.3.4.4.Egress from Dwelling Units permalink →
(1) Except as required by Sentence (8), single storey dwelling units in an apartment building need not lead to a public
corridor or exterior passageway on the same storey provided the dwelling units are served by private stairways leading
directly to a public access to exit on the storey
(a) immediately above, and
(b) immediately below.
(See Note A-3.3.4.4.(1))
(2) Except as required by Sentence (8) and as permitted by Sentences (3) and (4), a dwelling unit containing more than
one storey shall have an exit door or an egress door opening directly into a public access to exit from the uppermost storey
and from the lowest storey of the dwelling unit so that each of these storeys is served by an exit or egress door located not
more than 1.5 m above or below its floor level.
(3) A single exit is permitted from a dwelling unit provided the exit is an exterior doorway not more than 1.5 m above
adjacent ground level and
(a) it is not necessary to travel up or down more than one storey to reach the exit door, or
(b) the uppermost floor level opens to a balcony not more than 6 m above adjacent ground level.
(4) An egress door from either the uppermost storey or the lowest storey in a dwelling unit, as required by Sentence (2),
need not be provided
(a) except as required by Sentence (8), if that storey is served by a stairway that
(i) leads to a public access to exit,
(ii) has no direct access to any other storey in the dwelling unit, and
(iii) is separated from the other storeys in the dwelling unit by a fire separation having a fire-resistance rating of
not less than 45 min,
(b) on the uppermost storey in the dwelling unit if the dwelling unit has not more than 2 storeys above the first storey of
the building,
(c) if it is not necessary to travel either more than 18 m or more than 1 storey up or down within the dwelling unit to
reach the egress door, or
(d) if that storey is
(i) provided with a balcony conforming to Sentence (7),
(ii) not more than 2 storeys above or below the dwelling unit egress door, and
(iii) in a building that is not more than 6 storeys in building height.
(5) In a building of residential occupancy not more than 3 storeys in building height, a doorway from a dwelling unit is
permitted to open directly into an exit stairway provided the dwelling unit has a second and separate means of egress.
(6) If a dwelling unit has a second and separate means of egress, one means of egress from a dwelling unit is permitted
to pass through
(a) an interior corridor served by a single exit,
(b) an exterior balcony served by a single exit stairway, or
(c) an exterior passageway served by a single exit stairway.
(7) Where a balcony is provided to meet the requirements of Sentence (3) or (4), the balcony shall have
(a) a solid floor having a fire-resistance rating not less than that required for a floor assembly between suites, and
(b) an area providing not less than 1.5 m2 per suite occupant, based on occupant load, and a minimum dimension of
1 200 mm.
(8) Each dwelling unit in a building conforming to Subclause 3.2.2.50.(1)(a)(ii) shall be served by
(a) a direct exit that is an exterior doorway located not more than 1.5 m above adjacent ground level, or
(b) a stairway that
(i) leads to an exterior doorway not more than 1.5 m above adjacent ground level,
(ii) has no access to another dwelling unit, and
(iii) is separated from the remainder of the building with a fire separation having a fire-resistance rating not less
than 1 h.
3.3.4.5.Automatic Locking Prohibition permalink →
(1) Except for hotels, a door opening onto a public corridor that provides access to exit from a suite shall be designed
not to lock automatically. (See Note A-3.3.4.5.(1))
3.3.4.6.Sound Transmission permalink →
(1) Buildings containing dwelling units shall be constructed so that airborne noise is controlled in conformance with
Section 5.8.
3.3.4.7.Stairs, Ramps, Landings, Handrails and Guards for Dwelling Units permalink →
(1) Except as required in Article 3.3.4.8., stairs, ramps, landings, handrails and interior guards within a dwelling unit
shall conform to the applicable requirements in Section 9.8.
(2) Except as provided in Sentence (3), exterior stairs, ramps, landings, handrails and guards serving a single dwelling
unit shall conform to the applicable requirements in Sentence 3.1.21.1.(1) and Section 9.8.
(3) Loads on exterior guards serving a single dwelling unit shall comply with Part 4.
3.3.4.8.Protection of Openable Windows permalink →
(1) Except as provided in Sentence (2), openable windows in suites of residential occupancy shall be protected by
(a) a guard with a minimum height of 1 070 mm constructed in accordance with Article 3.3.1.18., or
(b) a mechanism that can only be released with the use of tools or special knowledge to control the free swinging or
sliding operation of the openable part of the window so as to limit any clear unobstructed opening to not more than
100 mm measured either vertically or horizontally.
(2) Windows need not be protected in accordance with Sentence (1) where
(a) the only opening having greater dimensions than those allowed by Clause (1)(b) is located higher than 1 070 mm
above the finished floor, or
(b) the bottom edge of the openable portion of the window is located less than 1 800 mm above the floor or ground on
the other side of the window.
3.3.4.9.Stud Wall Reinforcement permalink →
(1) If wood wall studs or sheet steel wall studs enclose the main bathroom in a dwelling unit, reinforcement shall be
installed to permit the future installation of the following:
(a) for a water closet, a grab bar described in Clauses 3.8.3.8.(3)(a) and a grab bar described in Clause 3.8.3.8.(3)(c),
(b) for a shower, grab bars described in Clause 3.8.3.13.(2)(g), and
(c) for a bathtub, grab bars described in Clause 3.8.3.13.(7)(e).
(See Note A-3.3.4.9.(1))
3.3.4.10.Resistance to Forced Entry permalink →
(1) Resistance to forced entry into dwelling units shall conform to the applicable requirements in Articles 9.7.5.2. and
9.7.5.3.
3.3.4.11.Retirement Homes permalink →
(1) Floor areas containing residents’ sleeping rooms in a retirement home shall conform to Sentences (2) to (12).
(2) Except as permitted by Sentence (3), a floor area containing residents’ sleeping rooms in a retirement home where
sleeping accommodation is provided for more than 10 residents shall be divided into no fewer than 2 fire compartments,
each not more than 1 000 m2 in area.
(3) The floor area on either side of a horizontal exit conforming to Article 3.4.6.10. is permitted to be considered as a
fire compartment in applying the requirements of this Article.
(4) Except as permitted by Sentence (5), fire separations separating fire compartments required by Sentence (2) shall
have a fire-resistance rating not less than 1 h.
(5) The fire-resistance rating of a fire separation referred to in Sentence (4) is permitted to be less than 1 h but not less
than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for
(a) the floor assembly above the floor area, or
(b) the floor assembly below the floor area, if there is no floor assembly above.
(6) A closure in a fire separation between fire compartments referred to in Sentence (2) shall be weather-stripped or
otherwise designed and installed to retard the passage of smoke.
(7) The travel distance from any point within each fire compartment referred to in Sentence (2) to a door to an adjoining
fire compartment shall be not more than 45 m.
(8) Each fire compartment referred to in Sentence (2) shall be capable of accommodating, in addition to its own
occupants, the occupants of the largest adjacent fire compartment based on a clear floor space of 1.5 m 2 per resident in the
adjacent fire compartment.
(9) The fire separation required by Sentence 3.3.5.5.(1) between a retirement home and a repair garage shall have no
openings.
(10) In a retirement home, a dead-end public corridor is permitted provided it is not more than 3 m long.
(11) The minimum clear width of doorways serving residents in a retirement home shall be 850 mm.
(12) A voice communication system conforming to Article 3.2.4.22. shall be provided in a retirement home.
3.3.5.Industrial Occupancy
(1) This Subsection applies to industrial occupancies.
3.3.5.2.Fire Extinguishing Systems permalink →
(1) In addition to other requirements in this Division for the installation of automatic fire extinguishing systems, an
appropriate fire extinguishing system shall be installed in every industrial occupancy floor area to provide protection if
required by
(a) the Fire Code made under the Fire Protection and Prevention Act, 1997, or
(b) the CCBFC NRCC-CONST-56437E, “National Fire Code of Canada,” in the absence of provisions referred to in
Clause (a).
(1) A basement shall not be used for the storage, manufacture or handling of volatile solids, liquids or gases that
generate explosive air-vapour mixtures or for processes that involve explosive dusts.
(2) Entrances and exits to a basement and to rooms containing building services shall be separate from the remainder of
the building in a building in which
(a) the storage, manufacture or handling of volatile materials can generate explosive air-vapour mixtures, or
(b) processes occur that produce explosive dusts.
(3) Basements and rooms referred to in Sentence (2) shall be separated from the remainder of the building with a
vapour-tight separation.
3.3.5.4.Repair and Storage Garages (See Note A-3.3.5.4.) permalink →
(1) If access is provided from a storage garage to a stair tower or elevator serving occupancies above the level of the
storage garage, the access shall be through a vestibule conforming to Sentence 3.3.5.7.(4).
(2) Treads and landings in interior stairs that extend to the roof of a storage garage shall be designed to be free of
accumulations of ice and snow.
(3) A mechanical storage garage not more than 4 storeys in building height, in which no persons other than parking
attendants are permitted above the street floor level, need not have a fire separation between the exits and the remainder
of the building.
(4) A storage garage or repair garage shall be provided with natural or mechanical ventilation in conformance with the
requirements of Subsection 6.3.1. and Article 6.9.1.2. to prevent excessive accumulation of carbon monoxide, exhaust
fumes or flammable and toxic vapours.
(5) Except as required by Sentence 3.8.2.2.(2), the clear height in a storage garage shall be not less than 2 m.
(6) Where storage garage or repair garage floors or ramps are 600 mm or more above the adjacent ground or floor
level, every opening through such floors and the perimeter of such floors and ramps shall be provided with
(a) a continuous curb not less than 140 mm high, a guard not less than 1 070 mm high and a vehicle guardrail not less
than 500 mm high conforming to Sentence (7), or
(b) a full-height wall conforming to Sentence (7).
(7) Vehicle guardrails and full-height walls required in Sentence (6) shall be designed and constructed to withstand the
loading values specified in Sentence 4.1.5.15.(1).
(8) Except for open-air storeys, every storey of a storage garage or repair garage located below grade shall be
sprinklered.
3.3.5.5.Repair Garage Separation permalink →
(1) A repair garage and any ancillary spaces serving it, including waiting rooms, reception rooms, tool and parts
storage areas and supervisory office space, shall be separated from other occupancies by a fire separation having a fire-
resistance rating not less than 2 h.
3.3.5.6.Storage Garage Separation permalink →
(1) Except as permitted by Sentences 3.3.4.2.(4) and (5), a storage garage shall be separated from other occupancies by
a fire separation with a fire-resistance rating not less than 1.5 h.
(1) If access is provided through a fire separation between a storage garage and a Group A, Division 1 or Group B
occupancy or a retirement home, the access shall be through a vestibule conforming to Sentence (4).
(2) Reserved.
(3) In a building more than 3 storeys in building height, access through a fire separation between a storage garage and
a Group A, Division 2, 3 or 4, or a Group C occupancy, shall be through a vestibule conforming to Sentence (4).
(4) If access is provided through a vestibule, as required by Sentences (1), (3) and 3.3.5.4.(1), the vestibule shall
(a) be not less than 1.8 m long,
(b) be ventilated
(i) naturally to outside air by a vent that has an unobstructed area of not less than 0.1 m 2 for each door that opens
into the vestibule but not less than 0.4 m², or
(ii) mechanically at a rate of 14 m3/h for each square metre of vestibule floor surface area, and
(c) have openings between the vestibule and an adjoining occupancy provided with self-closing doors with no hold-
open devices.
3.3.5.8.Reserved
3.3.5.9.Reserved
(1) Except where they serve storage garages, guards in industrial occupancies are permitted to consist of
(a) a top rail, and
(b) one or more intermediate rails spaced such that the openings through the guard are of a size that prevents the
passage of a spherical object whose diameter is 535 mm.
3.3.5.11.Toe-Boards Required permalink →
(1) Where tools or other objects could fall from the floor of an upper level to a lower level in a room or space intended
for use as a Group F occupancy, the edge of the floor at the upper level shall be provided with a toe-board extending from
the floor surface to a height at least 125 mm above the floor surface.
3.3.6.Design of Hazardous Areas
(1) This Subsection applies to design and fire protection requirements for buildings or parts of buildings intended for the
storage, handling, use and processing of
(a) dangerous goods,
(b) materials that involve a risk of explosion or high flammability, and
(c) materials that are highly reactive.
(See Note A-3.3.6.1.(1))
3.3.6.2.Storage of Dangerous Goods permalink →
(1) Solid and liquid dangerous goods classified as oxidizers or organic peroxides shall be separated from the remainder
of the building by a fire separation having a fire-resistance rating of not less than 2 h.
(2) Reactive materials shall be separated from the remainder of the building by a fire separation having a fire-resistance
rating of not less than 2 h. (See Note A-3.3.6.2.(2))
(3) The design and construction of buildings or part of a building intended for the storage of dangerous goods classified
as explosives shall conform to the Explosives Act (Canada) and the regulations made under that Act.
3.3.6.3.Indoor Storage of Compressed Gases permalink →
(1) Except as provided by Sentence (3), where required by the Fire Code made under the Fire Protection and
Prevention Act, 1997, a room intended for the indoor storage of cylinders containing flammable compressed gases shall
meet the following requirements:
(a) it is separated from the remainder of the building by a gas-tight fire separation having a fire-resistance rating of not
less than 2 h,
(b) it is located on an exterior wall of the building,
(c) it can be entered from the exterior,
(d) it is ventilated in conformance with Sentence (4),
(e) it is constructed so that an exterior wall provides explosion venting
(i) in the ratio of 0.2 m2 for each cubic metre of room volume, or
(ii) in the ratio computed in accordance with NFPA 68, “Standard on Explosion Protection by Deflagration
Venting,” but in no case less than 0.065 m2 of vent area for each cubic metre of room volume,
(f) it is not intended to contain fuel-fired equipment or high temperature heating elements, and
(g) it is not intended to be used for a purpose other than the storage of compressed gas.
(2) Where a closure is installed in the fire separation separating the room from the remainder of the building in
accordance with Clause (1)(a), it shall be
(a) equipped with a self-closing device that keeps the closure closed when not in use, and
(b) constructed so as to prevent the migration of gases from the room into other parts of the building.
(3) Where required by the Fire Code made under the Fire Protection and Prevention Act, 1997, a room intended for the
storage of not more than three cylinders of flammable compressed gases that are heavier than air and that have an
aggregate capacity not exceeding 100 kg shall be
(a) separated from the remainder of the building by a gas-tight fire separation having a fire-resistance rating of not less
than 45 min,
(b) located at or above grade, and
(c) ventilated in conformance with Sentence (4).
(4) A room described in Sentence (1) or (3) shall be
(a) mechanically vented to the outside so as to ensure at least one air change per hour, or
(b) naturally vented to the outside so as to ensure cross ventilation through non-closable louvered openings with
(i) at least one opening having an aggregate free opening area of at least 0.2 m 2 per 100 m2 of the floor area
located not more than 300 mm from the ceiling, and
(ii) at least one opening having an aggregate free opening area of at least 0.2 m 2 per 100 m2 of the floor area
located not more than 300 mm from the floor.
(5) Except as permitted by Sentences (6) and (7), where required by the Fire Code made under the Fire Protection and
Prevention Act, 1997, an area intended for the storage of cylinders containing compressed gases that may react with one
another shall be divided into separate fire compartments having a fire-resistance rating of not less than 1 h.
(6) Separate fire compartments required by Sentence (5) need not be provided, if the area intended for the storage of
cylinders containing compressed gases that are lighter than air is separated by a concrete or masonry wall having a height
of at least 2.0 m and projecting at least 1.0 m, measured horizontally, beyond the cylinders.
(7) Separate fire compartments required by Sentence (5) need not be provided, if the area intended for the storage of
cylinders containing compressed gases that are heavier than air is separated by a concrete or masonry wall having a height
of at least 1.5 m and projecting such that the minimum distance that vapour can travel between two cylinders of gas that
may react with each other is not less than 15 m, measured horizontally.
3.3.6.4.Storage and Dispensing Rooms for Flammable Liquids permalink →
and Combustible Liquids
(1) A room intended for the storage of flammable liquids and combustible liquids shall be separated from the remainder
of the building by a fire separation having a fire-resistance rating in conformance with the Fire Code made under the
Fire Protection and Prevention Act, 1997.
(2) Except as provided by Sentences (3) and (4), a room intended for the storage or dispensing of Class IA or Class IB
liquids in open containers shall be designed to prevent critical structural and mechanical damage from an internal
explosion in accordance with good engineering practice, such as that described in NFPA 68, “Standard on Explosion
Protection by Deflagration Venting.” (See Note A-3.3.6.4.(2))
(3) Sentence (2) does not apply to a room intended for the storage of distilled beverage alcohol.
(4) A room in an occupancy or facility covered by Regulation 851 of the Revised Regulations of Ontario, 1990
(Industrial Establishments), made under the Occupational Health and Safety Act, or Ontario Regulation 67/93 (Health
Care and Residential Facilities), made under that Act, where Class IA liquids are intended to be stored in closed
containers or Class I liquids are intended to be dispensed or stored in open containers, shall be designed to prevent critical
structural and mechanical damage from an internal explosion in accordance with good engineering practice, such as that
described in NFPA 68, “Standard on Explosion Protection by Deflagration Venting.”
(5) A dispensing room in an occupancy or facility described in Sentence (4) which has an area greater than 15 m 2 or in
which the travel distance from any point to the nearest egress door is more than 4.5 m shall
(a) be located in a floor area that has at least two exits, and
(b) have at least two egress doors.
(6) An egress door serving a room described in Sentence (5) shall
(a) be equipped with a self-closing device, and
(b) swing on a vertical axis in the direction of travel to the exit.
(7) The minimum distance between the egress doors described in Clause (5)(b) shall be not less than three-quarters of
the maximum diagonal dimension of the room.
(8) The travel distance within the room to the nearest egress door described in Clause (5)(b) shall be not more than
23 m.
(1) A tire storage area intended for the storage of more than 375 m 3 of tires shall be separated from the remainder of the
building by a fire separation having a fire-resistance rating of not less than 2 h. (See Note A-3.3.6.5.(1))
3.3.6.6.Ammonium Nitrate Storage permalink →
(1) Where the Fire Code made under the Fire Protection and Prevention Act, 1997 applies due to the quantity and
nature of the stored product, a building intended for the storage of ammonium nitrate shall
(a) be not more than one storey in building height,
(b) not contain a basement or a crawl space,
(c) not contain open floor drains, tunnels, elevator pits or other pockets that might trap molten ammonium nitrate,
(d) have noncombustible flooring materials in storage areas,
(e) be designed to prevent the ammonium nitrate from coming into contact with building materials that
(i) will cause the ammonium nitrate to become unstable,
(ii) may corrode or deteriorate by reason of contact with the ammonium nitrate, or
(iii) will become impregnated with the ammonium nitrate, and
(f) have not less than 0.007 m2 of vent area for each square metre of storage area, unless mechanical ventilation is
provided.
(See Note A-3.3.6.6.(1))
3.3.6.7.Flooring Materials permalink →
(1) Floors in areas where dangerous goods are stored shall be constructed of impermeable materials to prevent the
absorption of chemicals.
3.3.6.8.Fire Separations in Process Plants permalink →
(1) In process plants, areas where unstable liquids are handled or where small-scale unit chemical processes occur shall
be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 2 h.
3.3.6.9.Basements and Pits permalink →
(1) Process plants where Class I and II flammable liquids and combustible liquids are handled shall not be constructed
with basements or covered pits.
Understand any provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Try BUILDAiD Beta
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.