3.3.3.2.Fire Separations
(1) The fire separation required by Sentence 3.3.5.5.(1) between a care, care and treatment or detention occupancy and
a repair garage shall have no openings.
(2) Except as permitted by Sentence (4), in a Group B, Division 3 occupancy, walls between sleeping rooms and
adjacent rooms shall be constructed as fire separations having a fire-resistance rating not less than 1 h, except that the
fire-resistance rating need not be more than 45 min where the floor assembly is not required to be more than 45 min.
(3) Except as permitted by Sentence (4), in a Group B, Division 3 occupancy, walls separating corridors serving
sleeping rooms from adjacent rooms shall be constructed as fire separations having a fire-resistance rating not less than
1 h, except that the fire-resistance rating need not be more than 45 min where the floor assembly is not required to be
more than 45 min.
(4) The walls separating sleeping rooms from adjacent rooms and corridors in those parts of a floor area classified as a
Group B, Division 3 occupancy shall be constructed as fire separations but are not required to have a fire-resistance
rating if
(a) those parts of the floor area contain sleeping accommodation for not more than 10 persons, and
(b) not more than 6 occupants require assistance in evacuation in case of an emergency.
(5) The door in the fire-separation required in Sentence (4) is permitted to be equipped with a roller latch and need not
be provided with a self-closing device.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.