PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code

3.3.1.1.Separation of Suites

(1) Except as permitted by Sentences (2) and (3), each suite in other than business and personal services occupancies shall be separated from adjoining suites by a fire separation having a fire-resistance rating not less than 1 h. (See also Subsection 3.3.3. for care, care and treatment or detention occupancies, Article 3.3.4.2. for residential occupancies, and Article 3.1.8.7. for fire dampers.) (2) The fire-resistance rating of the fire separation required by Sentence (1) is permitted to be less than 1 h but not less than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for (a) the floor assembly above the floor area, or (b) the floor assembly below the floor area, if there is no floor assembly above. (3) Occupancies that are served by public corridors conforming to Clause 3.3.1.4.(4)(b) in a building that is sprinklered throughout, are not required to be separated from one another by fire separations provided the occupancies are (a) suites of business and personal services occupancy, (b) fast food vending operations that do not provide seating for customers, (c) suites of mercantile occupancy, or (d) any combination of these occupancies.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.