PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.3.1.24.Obstructions
(1) No obstruction shall be permitted in any occupancy that would restrict the width of a normal means of egress from
any part of a floor area to less than 750 mm unless an alternative means of egress is provided adjacent to, accessible
from, and plainly visible from the obstructed means of egress. (See Note A-3.3.1.24.(1))
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.