3.3.1.21.Exhaust Ventilation and Explosion Venting
(1) Except as provided in Sentence (2), an exhaust ventilation system designed in conformance with the appropriate
requirements of Part 6 shall be provided in a building or part of a building in which dust, fumes, gases, vapour or other
impurities or contaminants have the potential to create a fire or explosion hazard. (See also Article 4.2.4.13.)
(2) Where a fire separation required to have a fire-resistance rating is penetrated by a ventilation system required by
Sentence (1) for power-ventilated enclosures in laboratories, the ducts shall be
(a) continuously enclosed from the first penetrated fire separation to any subsequent fire separations or concealed
spaces and all the way through to the outdoors so that the highest fire-resistance rating of all the penetrated fire
separations is maintained, and
(b) exempted from the requirement to be equipped with a fire damper, smoke damper and combination smoke/fire
damper as stated in Article 3.1.8.7.
(3) Explosion relief devices, vents or other protective measures conforming to Subsection 6.3.1. and Article 6.9.1.2.
shall be provided for a space in which substances or conditions that have the potential to create an explosion hazard are
present as a result of the principal use of a building.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.