PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.3.1.8.Headroom and Protruding Objects
(1) Except within the floor area of a storage garage, the minimum headroom clearance in every access to exit shall
conform to the requirements of Article 3.4.3.4. for exits. (See also Sentence 3.3.5.4.(5))
(2) Except as permitted by Sentence (3) and except for paths of travel in service rooms and dwelling units, protruding
building elements located within 1 980 mm of the floor shall not project more than 100 mm horizontally into paths of
travel in a manner that would create a hazard. (See Note A-3.3.1.8.(2) and (3))
(3) The horizontal projection of a protruding building element referred to in Sentence (2) is permitted to be more than
100 mm, provided the clearance between the protruding element and the floor is less than 680 mm. (See Note A-
3.3.1.8.(2) and (3))
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.