3.3.6.2.Storage of Dangerous Goods
(1) Solid and liquid dangerous goods classified as oxidizers or organic peroxides shall be separated from the remainder
of the building by a fire separation having a fire-resistance rating of not less than 2 h.
(2) Reactive materials shall be separated from the remainder of the building by a fire separation having a fire-resistance
rating of not less than 2 h. (See Note A-3.3.6.2.(2))
(3) The design and construction of buildings or part of a building intended for the storage of dangerous goods classified
as explosives shall conform to the Explosives Act (Canada) and the regulations made under that Act.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.