3.3.3.6.Protection for Special Care and Treatment Facilities
(1) Compartments containing rooms such as operating rooms, recovery rooms, delivery rooms, intensive care units and
critical care units, from which it is impracticable to move patients in an emergency, shall be
(a) separated from adjacent spaces by fire separations having a fire-resistance rating not less than 1 h, and
(b) provided with a mechanical air supply so that during a period of 2 h after the start of a fire in another space, the
compartments will not contain more than 1% by volume of contaminated air from the fire area.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.