What is the minimum corridor width under the Ontario Building Code?
Public corridors must be at least 1 100 mm (about 43 in) wide, with wider minimums for some uses such as care and treatment occupancies, and the width must also satisfy the occupant load calculation of 6.1 mm per person.
Paraphrased for clarity — open this provision in the BUILDAiD Library for the exact wording.
On most projects 1 100 mm governs, but always verify the occupant-load-based width for heavily populated floors and the enhanced widths for hospitals and long-term care, where bed movement demands more. Watch for door swings, radiators, fountains and handrail projections eating into clear width; the Code limits how far obstructions may project. Barrier-free path of travel requirements in Section 3.8 can also push corridors wider than the fire-safety minimum.
Hallways that people share in a building must be at least about 1.1 m wide so everyone can get out quickly, even passing others. Hospitals and care homes need wider hallways to move beds and wheelchairs.
Get answers like this for any code question
BUILDAiD Assist searches the building code and answers in plain English with exact citations — in seconds.
This page is provided for general information. Building code requirements depend on your specific project, occupancy and municipality, and code editions change. Always verify requirements against the current Ontario Building Code and confirm with your local building department.