(1) Except as permitted by Sentence (2), a library book storage room that is not normally accessible to the public shall
be separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 2 h if it
(a) is more than 250 m2 in area, or
(b) contains book stacks that
(i) are more than 10 m high, or
(ii) penetrate more than one floor assembly.
(2) The fire separation required by Sentence (1) is not required if the book storage room is sprinklered.
(3) Open book shelves are permitted above and below a mezzanine floor in a library building provided the height of the
shelves is not more than 2.1 m but not more than 75% of the floor-to-ceiling height of the space above or below the
mezzanine floor assembly.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.