3.3.4.3.Storage Rooms
(1) Sprinklers shall be installed in a storage room provided for the use of tenants in a residential occupancy within a
floor area but not contained within a suite.
(2) Except as permitted by Sentence (3), a storage room referred to in Sentence (1) shall be separated from the
remainder of the building by a fire separation having a fire-resistance rating not less than 1 h.
(3) The fire-resistance rating of the fire separation required by Sentence (2) is permitted to be less than 1 h but not less
than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for
(a) the floor assembly above the floor area, or
(b) the floor assembly below the floor area, if there is no floor assembly above.
(4) Except where located within a dwelling unit, a room intended for the storage of flammable liquids or combustible
liquids required by the Fire Code made under the Fire Protection and Prevention Act, 1997 shall not be located above or
below the first storey of the building.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.