OBC DIVISION B · PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Section 9.26 — Roofing
Full text of Section 9.26 (Roofing) — Division B, Part 9 (Housing and Small Buildings) of the 2024 Ontario Building Code, with every article reproduced below.
9.26.1.General
(1) For the purpose of this Section, the term “roof” shall mean sloped or near-horizontal assemblies that protect the
spaces beneath them, including platforms that effectively serve as roofs with respect to the accumulation or drainage of
precipitation. (See Note A-9.26.1.1.(1))
(2) For the purpose of this Section, the term “roofing” shall mean the primary covering for roofs.
9.26.1.2.Required Protection permalink →
(1) Roofs shall be protected with roofing, including flashing, installed so as to
(a) effectively shed water,
(b) prevent the ingress of water and moisture into building assemblies and occupied space, and
(c) minimize the ingress of water due to ice damming into building assemblies.
(2) Compliance with Sentence (1) shall be demonstrated by conforming to
(a) this Section, or
(b) Part 5.
9.26.1.3.Alternate Installation Methods permalink →
(1) Methods described in CSA A123.51, “Asphalt shingle application on roof slopes 1:6 and steeper,” are permitted to
be used for the installation of asphalt shingles in lieu of the methods described in this Section.
9.26.1.4.Solar Collector Systems permalink →
(1) A solar collector system is permitted to be installed above roofing materials conforming to Sentence 9.26.2.1.(1).
9.26.2.Roofing Materials
9.26.2.1.Material Standards permalink →
(1) Where materials used for the preparation of the substrate for roofing are covered in the scope of a standard listed in
Table 9.26.2.1.-A, they shall conform to that standard.
(2) Where roofing materials are covered in the scope of a standard listed in Table 9.26.2.1.-B, they shall conform to that
standard.
Table 9.26.2.1.-A
Materials for Preparation of the Substrate for Roofing
Forming Part of Sentence 9.26.2.1.(1)
Type of Material Standards
Sheathing Membranes CAN/CGSB-51.32-M, “Sheathing, Membrane, Breather Type”
Primers CGSB 37-GP-9Ma, “Primer, Asphalt, Unfilled, for Asphalt Roofing, Dampproofing and Waterproofing”
Table 9.26.2.1.-B
Roofing Materials
Forming Part of Sentence 9.26.2.1.(2)
Type of Roof Covering Standards
ASTM D3019 / D3019M, “Standard Specification for Lap Cement Used with Asphalt Roll Roofing,
Non-Fibered and Fibered” (1)
ASTM D4479 / D 4479M, “Standard Specification for Asphalt Roof Coatings - Asbestos-Free”
CAN/CGSB-37.50-M, “Hot-Applied, Rubberized Asphalt for Roofing and Waterproofing”
CGSB 37-GP-56M, “Membrane, Modified, Bituminous, Prefabricated, and Reinforced for Roofing”
Built-up roofing (BUR) CAN/CSA-A123.2, “Asphalt-Coated Roofing Sheets”
CSA A123.3, “Asphalt Saturated Organic Roofing Felt”
CAN/CSA-A123.4, “Asphalt for Constructing Built-Up Roof Coverings and Waterproofing Systems”
CSA A123.17, “Asphalt Glass Felt Used in Roofing and Waterproofing”
CSA A123.23, “Product specification for polymer-modified bitumen sheet, prefabricated and
reinforced”
ASTM D4637 / D4637M, “Standard Specification for EPDM Sheet Used In Single-Ply Roof
Membrane”
ASTM D4811 / D4811M, “Standard Specification for Nonvulcanized (Uncured) Rubber Sheet Used
as Roof Flashing”
Single-ply membranes ASTM D6878 / D6878M, “Standard Specification for Thermoplastic Polyolefin Based Sheet Roofing”
CAN/CGSB-37.54, “Polyvinyl Chloride Roofing and Waterproofing Membrane”
CAN/CGSB-37.58-M, “Membrane, Elastomeric, Cold-Applied Liquid, for Non-
Exposed Use in Roofing and Waterproofing”
CSA A123.5, “Asphalt shingles made from glass felt and surfaced with mineral granules”
CAN/CSA-A220 Series, “Concrete Roof Tiles”
Shingles, shakes, tiles, panels
CSA O118.1, “Western Red Cedar Shakes and Shingles”
CSA O118.2, “Eastern White Cedar Shingles”
CAN/CSA-A123.16, “Asphalt-coated glass-base sheets”
Eave protection CSA A123.22, “Self-Adhering Polymer Modified Bituminous Sheet Materials Used as Steep Roofing
Underlayment for Ice Dam Protection”
ASTM D4811 / D4811M, “Standard Specification for Nonvulcanized (Uncured) Rubber Sheet Used
Flashing
as Roof Flashing”
Notes to Table 9.26.2.1.-B:
(1) For the purpose of this Subsection, ASTM D3019 / D3019M shall only apply to the non-fibered and non-asbestos-fibered types (I and
III) of asphalt roll roofing.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.26.2.2.Installation of Materials permalink →
(1) Materials listed in Tables 9.26.2.1.-A and 9.26.2.1.-B shall be installed in conformance with the manufacturer's
written instructions. (See Sentence 1.5.1.2.(1) of Division A)
(1) Nails used for roofing shall be corrosion-resistant roofing or shingle nails conforming to
(a) ASTM F1667, “Standard Specification for Driven Fasteners: Nails, Spikes, and Staples,” or
(b) CSA B111, “Wire Nails, Spikes and Staples.”
(2) Nails shall have sufficient length to penetrate through or 12 mm into, roof sheathing.
(3) Nails used with asphalt roofing shall have a head diameter of not less than 9.5 mm and a shank thickness of not less
than 2.95 mm.
(4) Nails used with wood shingles or shakes shall have a head diameter of not less than 4.8 mm and a shank thickness of
not less than 2.0 mm and shall be stainless steel, aluminum or hot-dipped galvanized. (See Note A-9.26.2.3.(4))
(1) Staples used to apply asphalt or wood shingles shall be corrosion-resistant and shall be driven with the crown
parallel to the eaves.
(2) Staples used with asphalt shingles shall be not less than 19 mm long, 1.6 mm diam or thickness, with not less than a
25 mm crown, except that an 11 mm crown may be used as provided in Sentence 9.26.7.4.(2).
(3) Staples used with wood shingles shall be not less than 29 mm long, 1.6 mm diam or thickness, with not less than a
9.5 mm crown and shall be stainless steel or aluminum. (See Note A-9.26.2.3.(4))
9.26.3.Slope of Roof Surfaces
(1) Except as provided in Sentences (2) and (3), the slopes on which roof coverings may be applied shall conform to
Table 9.26.3.1.
(2) Asphalt and gravel or coal tar and gravel roofs may be constructed with lower slopes than required in Sentence (1)
when effective drainage is provided by roof drains located at the lowest points on the roofs.
(3) Profiled metal roof cladding systems specifically designed for low-slope applications are permitted to be installed
with lower slopes than required in Sentence (1), provided they are installed in conformance with the manufacturer’s
written recommendations.
(4) Except where back-slope will not adversely affect adjacent supported or supporting constructions due to water
ingress, roofs and constructions that effectively serve as roofs shall be constructed with sufficient slope away from
(a) exterior walls, and
(b) guards that are connected to the roof, or to a construction that effectively serves as a roof, by more than pickets or
posts.
(See Notes A-9.26.1.1.(1), A-9.26.4.1. and A-9.27.3.8.(4))
(5) The slope required in Sentence (4) shall be sufficient to maintain a positive slope
(a) after expected shrinkage of the building frame, where these surfaces are supported by exterior walls and on exterior
columns, and (See Note A-9.27.3.8.(4))
(b) once design loading is taken into consideration, where these surfaces are cantilevered from exterior walls.
Table 9.26.3.1.
Roofing Types and Slope Limits
Forming Part of Sentence 9.26.3.1.(1)
Type of Roofing Minimum Slope Maximum Slope
Asphalt Shingles
Low slope application 1 in 6 no limit
Normal application 1 in 3 no limit
Built-up Roofing
Asphalt base (without gravel) 1 in 25 1 in 2
Asphalt base (gravelled) 1 in 50(1) 1 in 4
Coal-tar base (gravelled) 1 in 50(1) 1 in 25
Cold process 1 in 25 1 in 1.33
Cedar Shakes 1 in 3 no limit
Clay Tile 1 in 2 no limit
Glass Fibre Reinforced Polyester Roofing Panels 1 in 4 no limit
Modified Bituminous Membranes 1 in 50 1 in 4
Profiled Metal Roofing 1 in 4(2) no limit
Roll Roofing
480 mm wide selvage asphalt roofing 1 in 6 no limit
Cold application felt 1 in 50 1 in 1.33
Smooth and mineral surfaced 1 in 4 no limit
Sheet Metal Shingles 1 in 4(2) no limit
Slate Shingles 1 in 2 no limit
Wood Shingles 1 in 4 no limit
Notes to Table 9.26.3.1.:
(1) See Sentence 9.26.3.1.(2).
(2) See Sentence 9.26.3.1.(3).
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.26.4.Flashing at Intersections
9.26.4.1.Required Flashing at Intersections (See Notes A-9.26.4.1. and A-9.26.1.1.(1)) permalink →
(1) Except where the omission of flashing will not adversely affect adjacent supported or supporting constructions,
flashing shall be installed at junctions between roofs and
(a) walls that rise above the roof, and
(b) guards that are connected to the roof by more than pickets or posts.
(1) Sheet metal flashing shall consist of not less than
(a) 1.73 mm thick sheet lead,
(b) 0.33 mm thick galvanized steel,
(c) 0.33 mm thick copper,
(d) 0.35 mm thick zinc, or
(e) 0.48 mm thick aluminum.
9.26.4.3.Valley Flashing permalink →
(1) Where sloping surfaces of shingled roofs intersect to form a valley, the valley shall be flashed.
(2) Valley flashing shall be installed over continuous sheathing.
(3) Closed valleys shall not be used with rigid shingles on slopes of less than 1 in 1.2.
(3.1) Closed valley flashing shall consist of sheet metal, self sealing composite membranes consisting of polyethylene and
bituminous material or one layer of either Type S smooth surface roll roofing or Type M mineral surface roll roofing
(mineral surface down) not less than 600 mm wide, and nails shall not penetrate the flashing within 75 mm of its edge or
124 mm of the bottom of the valley centre line.
(4) Open valleys shall be flashed with at least
(a) one layer of sheet metal not less than 600 mm wide, or
(b) 2 layers of roll roofing.
(5) The bottom layer of roofing required in Sentence (4) shall consist of at least Type S smooth roll roofing or Type M
mineral surface roll roofing (mineral surface down) not less than 457 mm wide, centred in the valley and fastened with
nails spaced not more than 450 mm o.c. located 25 mm away from the edges.
(6) The top layer of roofing required in Sentence (4) shall consist of at least Type M mineral surface roll roofing
(mineral surface up), 914 mm wide, centred in the valley, applied over a 100 mm wide strip of cement along each edge of
the bottom layer, and fastened with a sufficient number of nails to hold it in place until the shingles are applied.
9.26.4.4.Intersection of Shingle Roofs and Masonry permalink →
(1) The intersection of shingle roofs and masonry walls or chimneys shall be protected with flashing.
(2) Counter flashing required in Sentence (1) shall be embedded not less than 25 mm in the masonry and shall extend
not less than 150 mm down the masonry and lap the lower flashing not less than 100 mm.
(3) Flashing along the slopes of a roof described in Sentence (1) shall be stepped so that there is not less than a 75 mm
head lap in both the lower flashing and counter flashing.
(4) Where the roof described in Sentence (1) slopes upwards from the masonry, the flashing shall extend up the roof
slope to a point equal in height to the flashing on the masonry, but not less than 1.5 times the shingle exposure.
9.26.4.5.Intersection of Shingle Roofs and Walls Other Than Masonry permalink →
(1) The intersection of shingle roofs and walls clad with other than masonry shall be protected with flashing.
(2) Flashing required in Sentence (1) shall be installed so that it extends up the wall not less than 75 mm behind the
sheathing paper, and extends not less than 75 mm horizontally.
(3) Along the slope of the roof, the flashing required in Sentence (1) shall be stepped with not less than a 75 mm head
lap.
9.26.4.6.Intersection of Built-Up Roofs and Masonry permalink →
(1) The intersection of built-up roofs with masonry walls or chimneys shall have a cant strip at the intersection and a
roofing membrane shall be mopped over the cant strip and not less than 150 mm up the wall.
(2) Counter flashing installed over the intersection referred to in Sentence (1) shall be embedded not less than 25 mm in
the masonry, and shall be of sufficient length to extend down not less than 150 mm, lapping the membrane on the
masonry not less than 100 mm.
9.26.4.7.Intersection of Built-Up Roofs and Walls Other Than Masonry permalink →
(1) The intersection of built-up roofs with walls clad with other than masonry shall have a cant strip at the intersection.
(2) The roofing membrane shall be mopped over the cant strip referred to in Sentence (1).
(3) Flashing plies shall extend not less than 150 mm up the wall referred to in Sentence (1) behind the sheathing paper.
9.26.4.8.Chimney Saddles permalink →
(1) Except as otherwise permitted in Sentence (5), chimney saddles shall be installed where the upper side of a chimney
on a sloping roof is more than 750 mm wide.
(2) Chimney saddles shall be covered with sheet metal or roofing material of weight and quality equivalent to the
roofing.
(3) Saddles shall be flashed where they intersect the roof.
(4) The intersection of the saddle and the chimney shall be flashed and counterflashed as described in Article 9.26.4.4.
(5) A chimney saddle need not be installed if the intersection between the chimney and roof is protected by sheet metal
flashing that extends up the chimney to a height equal to at least one-sixth the width of the chimney, but not less than
150 mm, and up the roof slope to a point equal in height to the flashing on the chimney, but not less than 1.5 times the
shingle exposure.
(6) Flashing described in Sentence (5) at the chimney shall be counterflashed as required by Article 9.26.4.4.
9.26.5.Eave Protection for Shingles and Shakes
9.26.5.1.Required Eave Protection permalink →
(1) Except as provided in Sentence (2), eave protection shall be provided on shingle, shake or tile roofs, extending from
the edge of the roof a minimum of 900 mm up the roof slope to a line not less than 300 mm inside the inner face of the
exterior wall.
(2) Eave protection is not required
(a) over unheated garages, carports and porches,
(b) where the roof overhang exceeds 900 mm measured along the roof slope from the edge of the roof to the inner face
of the exterior wall,
(c) on roofs of asphalt shingles installed in accordance with Subsection 9.26.8.,
(d) on roofs with slopes of 1 in 1.5 or greater, or
(e) in regions with 3 500 or fewer degree-days.
(1) Eave protection shall be laid beneath the starter strip and shall consist of
(a) No. 15 asphalt-saturated felt laid in two plies lapped 480 mm and cemented together with lap cement,
(b) Type M or S roll roofing laid with not less than 100 mm head and end laps cemented together with lap cement,
(c) glass fibre or polyester fibre coated base sheets, or
(d) self-sealing composite membranes consisting of modified bituminous coated material.
9.26.6.Underlay Beneath Shingles
(1) Except as required in Sentence (2), when underlay is used beneath shingles, it shall be
(a) asphalt-saturated sheathing paper weighing not less than 0.195 kg/m², or
(b) No. 15 plain or perforated asphalt-saturated felt.
(See Note A-9.26.6.1.(1))
(2) Underlay used beneath wood shingles shall be breather type.
(1) When used with shingles, underlay shall be installed parallel to the eaves with head and end lap of not less than
50 mm.
(2) The top edge of each strip of underlay referred to in Sentence (1) shall be fastened with sufficient roofing nails to
hold it in place until the shingles are applied.
(3) The underlay referred to in Sentence (1) shall overlap the eave protection by not less than 100 mm. (See Article
9.26.10.2.for underlay beneath wood shakes.)
9.26.7.Asphalt Shingles on Slopes of 1 in 3 or Greater
(1) Coverage shall be not less than 2 thicknesses of shingle over the entire roof, disregarding cutouts.
9.26.7.2.Starter Strip permalink →
(1) A starter strip shall be installed along the lower edge of the roof so that it extends approximately 12 mm beyond the
eaves and rake of the roof and fastened along the bottom edge with nails spaced not more than 300 mm o.c.
(2) Starter strips shall be
(a) at least Type M mineral-surfaced roll roofing not less than 300 mm wide,
(b) shingles of the same weight and quality as those used as a roof covering with tabs facing up the roof slope, or
(c) pre-manufactured starter strips installed with sealant at the eaves.
(3) Starter strips need not be provided where eave protection of not less than Type M mineral-surfaced roll roofing is
provided or self-sealing composite membranes consisting of polyethylene and bituminous material is provided.
(1) Shingles shall have a head lap of not less than 50 mm.
(1) Except as provided in Sentence (2), shingles shall be fastened with at least 4 nails or staples for 1 m wide shingles so
that no nails or staples are exposed.
(2) Where staples with an 11 mm crown are used, shingles shall be fastened with at least 6 staples.
(3) Fasteners may be reduced for narrower shingles in proportion to the width of the shingle or when shingles
incorporating interlocking devices are used.
(4) Fasteners referred to in Sentences (1) and (2) shall be located 25 mm to 40 mm from each end of each strip shingle
with other fasteners equally spaced between them.
(5) Fasteners referred to in Sentences (1) and (2) shall be located not less than 12 mm above the tops of the cutouts.
9.26.7.5.Securing of Tabs permalink →
(1) Shingle tabs shall be secured by a spot of plastic cement not exceeding 25 mm diam under the centre of each tab or
by interlocking devices or self-sealing strips.
9.26.7.6.Hips and Ridges permalink →
(1) Shingles on hips and ridges shall be applied so they extend not less than 100 mm on either side of the hip or ridge,
and shall be lapped not less than 150 mm.
(2) Shingles referred to in Sentence (1) shall be fastened with nails or staples on each side located not more than 25 mm
from the edge and 25 mm above the butt of the overlying shingle.
9.26.7.7.Eave Protection permalink →
(1) Eave protection shall conform to Subsection 9.26.5.
(1) Flashing shall conform to Subsection 9.26.4.
9.26.8.Asphalt Shingles on Slopes of Less Than 1 in 3
(1) Except for the first 2 courses, coverage shall be not less than 3 thicknesses of shingle over the entire roof,
disregarding cutouts.
9.26.8.2.Starter Strip permalink →
(1) A starter strip shall be installed as in Article 9.26.7.2.
(2) Starter strips required in Sentence (1) shall be laid in a continuous band of cement not less than 200 mm wide.
9.26.8.3.Securing of Tabs permalink →
(1) Shingle tabs shall be secured with cold application cement applied at the rate of not less than 0.5 L/m² of cemented
area, or hot application asphalt applied at the rate of 1 kg/m² of cemented area.
9.26.8.4.Securing of Shingle Courses permalink →
(1) The first course of shingles shall be secured by a continuous band of cement along the eaves applied so that the
width of the band equals the shingle exposure plus 100 mm.
(2) The succeeding courses of shingles shall be secured by a continuous band of cement applied so that the width of the
band equals the shingle exposure plus 50 mm.
(3) The band required in Sentence (2) shall be located not more than 50 mm above the butt of the overlying course of
shingles.
9.26.8.5.Hips and Ridges permalink →
(1) Shingles on hips and ridges shall be not less than 300 mm wide applied to provide triple coverage.
(2) Shingles referred to in Sentence (1) shall be cemented to the roof shingles and to each other with a coat of cement
and fastened with nails or staples located 40 mm above the butt of the overlying shingle and 50 mm from each edge.
(1) Flashing shall conform to Subsection 9.26.4.
(1) Shingles shall be fastened in accordance with Article 9.26.7.4.
9.26.9.Wood Roof Shingles
(1) Decking for wood shingled roofs may be continuous or spaced.
(1) Western cedar shingles shall be not less than No. 2 grade.
(2) Eastern white cedar shingles shall be not less than B (clear) grade.
(1) Wood shingles shall be not less than 400 mm long and not less than 75 mm nor more than 350 mm wide.
9.26.9.4.Spacing and Joints permalink →
(1) Shingles shall be spaced approximately 6 mm apart and offset at the joints in adjacent courses not less than 40 mm
so that joints in alternate courses are staggered.
(1) Shingles shall be fastened with 2 nails or staples located approximately 20 mm from the sides of the shingle and
40 mm above the exposure line.
(1) The exposure of wood roof shingles shall conform to Table 9.26.9.6.
Table 9.26.9.6.
Exposure of Wood Shingles
Forming Part of Sentence 9.26.9.6.(1)
Maximum Exposure, mm
Roof Slope No. 1 or A Grade Length of Shingle, mm No. 2 or B Grade Length of Shingle, mm
400 450 600 400 450 600
< 1 in 3 100 115 165 90 100 140
≥ 1 in 3 125 140 190 100 115 165
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
(1) Flashing shall conform to Subsection 9.26.4.
9.26.9.8.Eave Protection permalink →
(1) Eave protection shall conform to Subsection 9.26.5.
9.26.10.Cedar Roof Shakes
9.26.10.1.Size and Thickness permalink →
(1) Shakes shall be not less than 450 mm long and not less than 100 mm nor more than 350 mm wide with a butt
thickness of not more than 32 mm and not less than 9 mm.
(1) Where eave protection is not provided, an underlay conforming to the requirements in Article 9.26.6.1. for wood
shingles shall be laid as a strip not less than 900 mm wide along the eaves.
(2) A strip of material similar to that described in Sentence (1) not less than 450 mm wide shall be interlaid between
each course of shakes with the bottom edge of the strip positioned above the butt line at a distance equal to double the
exposure of the shakes.
(3) Interlaid strips referred to in Sentence (2) shall be lapped not less than 150 mm at hips and ridges in a manner at will
prevent water from reaching the roof sheathing.
9.26.10.3.Spacing and Joints permalink →
(1) Shakes shall be spaced 6 mm to 9 mm apart and the joints in any one course shall be separated not less than 40 mm
from joints in adjacent courses.
(1) Shakes shall be fastened with nails located approximately 20 mm from the sides of the shakes and 40 mm above the
exposure line.
(1) The exposure of wood shakes shall not exceed
(a) 190 mm for shakes not less than 450 mm long, and
(b) 240 mm for shakes not less than 600 mm long.
(1) Flashing shall conform to Subsection 9.26.4.
9.26.10.7.Eave Protection permalink →
(1) Eave protection shall conform to Subsection 9.26.5.
(1) Shakes shall be not less than No. 1 or Handsplit grade.
9.26.11.Built-Up Roofs
9.26.11.1.Quantity of Materials permalink →
(1) The quantities of bituminous materials used on built-up roofs shall conform to Table 9.26.11.1.
Table 9.26.11.1.
Quantities of Bitumen for Built-Up Roofs
Forming Part of Sentence 9.26.11.1.(1)
Amount of Bitumen per Square Metre of Roof Surface
Type of Roof
Mopping Coats Between Layers Flood Coat
Asphalt and aggregate 1 kg 3 kg
Coal-tar and aggregate 1.2 kg 3.6 kg
Cold process roofing 0.75 L cold process cement 2 L cold process top coating
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.26.11.2.Coal-Tar and Asphalt Products permalink →
(1) Coal-tar products and asphalt products shall not be used together in built-up roof construction.
(1) Bitumen roofing felts shall be at least No.15 felt.
9.26.11.4.Aggregate Surfacing permalink →
(1) Aggregate used for surfacing built-up roofs shall be clean, dry and durable and shall consist of particles of gravel,
crushed stone or air-cooled blast furnace slag having a size of from 6 mm to 15 mm.
(2) The minimum amount of aggregate surfacing per square metre of roof surface shall be 15 kg gravel or crushed stone
or 10 kg crushed slag.
(1) Flashing for built-up roofs shall conform to Subsection 9.26.4.
9.26.11.6.Number of Layers permalink →
(1) Built-up roofing shall consist of not less than 3 three mopped-down layers of roofing felt flood coated with bitumen.
9.26.11.7.Installation of Layers permalink →
(1) In hot process applications each layer of bitumen-saturated felt shall be laid while the bitumen is hot, with each layer
overlapping the previous one.
(2) The full width under each lap referred to in Sentence (1) shall be coated with bitumen so that in no place does felt
touch felt.
(3) Felt shall be laid free of wrinkles and shall be rolled directly into the hot bitumen and broomed forward and outward
from the centre to ensure complete adhesion.
9.26.11.8.Roofing Over Wood-Based Sheathing permalink →
(1) Except as permitted in Sentence (2), built-up roofing applied over wood, plywood, OSB or waferboard roof
sheathing shall be laid over an additional base layer of felt laid dry over the entire roof deck with not less than a 50 mm
headlap and a 50 mm sidelap between each sheet.
(2) Where plywood, OSB or waferboard roof sheathing is used, the dry layer of felt required in Sentence (1) may be
omitted when the joints are taped and the sheathing is primed with asphalt.
9.26.11.9.Attachment to Decking permalink →
(1) Roofing shall be securely attached to the decking or where insulation is applied above the deck, the insulation shall
be securely attached to the deck before the first layer of felt is fastened to the insulation.
9.26.11.10.Cant Strips permalink →
(1) Except as permitted in Sentence (4), a cant strip shall be provided at the edges of roofs.
(2) At least 2 plies of the roofing membrane shall be carried over the top of the cant strip.
(3) Flashing shall extend over the top of the cant strip and be shaped to form a drip.
(4) The cant strip required in Sentence (1) need not be provided where a gravel stop is installed at the edge of roofs.
(5) The roofing membranes shall be carried over the edge of the roof before the gravel stop referred to in Sentence (4) is
fastened and 2 plies of roofing membrane mopped to the top surface of the gravel stop before the flood coat is applied.
(6) The gravel stop referred to in Sentence (4) shall extend over the edge of the roof to form a drip or shall be flashed so
that the flashing extends over the edge to form a drip.
9.26.12.Selvage Roofing
(1) Wide selvage asphalt roofing shall provide double coverage over the entire roof surface.
(1) Plies of selvage roofing shall be cemented together to ensure a watertight joint.
9.26.13.Sheet Metal Roofing
(1) Sheet metal roofing shall be not less than
(a) 0.33 mm thick galvanized steel,
(b) 0.46 mm thick copper,
(c) 0.46 mm thick zinc, or
(d) 0.48 mm thick aluminum.
(1) Where sheet metal roofing is not supported by roof decking but spans between spaced supports, the panels shall be
designed to support the specified live loads for roofs.
9.26.14.Glass Reinforced Polyester Roofing
(1) Where glass reinforced polyester roofing panels are not supported by roof decking but span between spaced
supports, the panels shall be designed to support the specified roof loads.
9.26.15.Hot Applied Rubberized Asphalt Roofing
9.26.15.1.Installation permalink →
(1) Hot applied rubberized asphalt roofing shall be installed in accordance with CAN/CGSB-37.51-M, “Application for
Hot Applied Rubberized Asphalt for Roofing and Waterproofing”.
9.26.16.Polyvinyl Chloride Sheet Roofing
9.26.16.1.Installation permalink →
(1) Polyvinyl chloride sheet applied roofing membrane shall be installed in accordance with CGSB 37-GP-55M,
“Application of Sheet Applied Flexible Polyvinyl Chloride Roofing Membrane.”
9.26.17.Concrete Roof Tiles
9.26.17.1.Installation permalink →
(1) Concrete roof tiles shall be installed according to CAN/CSA-A220 Series, “Concrete Roof Tiles.” (See Note A-
9.26.17.1.(1))
9.26.18.Roof Drains and Downspouts
(1) When roof drains are provided they shall conform to Part 7.
(1) Where downspouts are provided and are not connected to a sewer, extensions shall be provided to carry rainwater
away from the building in a manner which will prevent soil erosion.
Understand any provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Try BUILDAiD Beta
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.