9.26.4.5.Intersection of Shingle Roofs and Walls Other Than Masonry
(1) The intersection of shingle roofs and walls clad with other than masonry shall be protected with flashing.
(2) Flashing required in Sentence (1) shall be installed so that it extends up the wall not less than 75 mm behind the
sheathing paper, and extends not less than 75 mm horizontally.
(3) Along the slope of the roof, the flashing required in Sentence (1) shall be stepped with not less than a 75 mm head
lap.
← Previous9.26.4.4. Intersection of Shingle Roofs and MasonryNext →9.26.4.6. Intersection of Built-Up Roofs and Masonry
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.