PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.26.4.6.Intersection of Built-Up Roofs and Masonry
(1) The intersection of built-up roofs with masonry walls or chimneys shall have a cant strip at the intersection and a
roofing membrane shall be mopped over the cant strip and not less than 150 mm up the wall.
(2) Counter flashing installed over the intersection referred to in Sentence (1) shall be embedded not less than 25 mm in
the masonry, and shall be of sufficient length to extend down not less than 150 mm, lapping the membrane on the
masonry not less than 100 mm.
← Previous9.26.4.5. Intersection of Shingle Roofs and Walls Other ThNext →9.26.4.7. Intersection of Built-Up Roofs and Walls Other T
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.