PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.26.10.2.Underlay
(1) Where eave protection is not provided, an underlay conforming to the requirements in Article 9.26.6.1. for wood
shingles shall be laid as a strip not less than 900 mm wide along the eaves.
(2) A strip of material similar to that described in Sentence (1) not less than 450 mm wide shall be interlaid between
each course of shakes with the bottom edge of the strip positioned above the butt line at a distance equal to double the
exposure of the shakes.
(3) Interlaid strips referred to in Sentence (2) shall be lapped not less than 150 mm at hips and ridges in a manner at will
prevent water from reaching the roof sheathing.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.