9.32.3.7.Supplemental Exhaust (See Note A-9.32.3.7.)
(1) Except as provided in Sentences (2) and (3), a supplemental exhaust fan with a rated capacity not less than 50 L/s
shall be installed in each kitchen.
(2) A supplemental exhaust fan is not required in a kitchen where the only exhaust air intake for the principal ventilation
fan is located in that kitchen.
(3) A supplemental exhaust fan is not required in a kitchen where the principal ventilation fan draws from that kitchen
and other rooms, provided
(a) the principal ventilation fan can be switched to a high exhaust rate equal to not less than 2.5 times the minimum
normal operating exhaust capacity specified in Table 9.32.3.3., and
(b) the high exhaust rate of the principal ventilation fan, as described in Clause (a), is activated by a manual switch in
the kitchen labeled “KITCHEN EXHAUST.”
(4) Where an exhaust air intake for the principal ventilation fan is not located in a bathroom or water-closet room, a
supplemental exhaust fan with a rated capacity not less than 25 L/s shall be installed in that bathroom or water-closet
room.
(5) Where the intake for a supplemental exhaust fan other than a cooking appliance exhaust fan serving a cooktop is
installed in a kitchen, it shall be installed in the ceiling or on the wall at not less than 2 m above the floor.
(6) A supplemental exhaust fan required by this Article shall be controlled by a manual switch located in the room
served by the fan.
(7) Where a kitchen or bathroom is exempted from the requirement to install a supplemental exhaust fan by virtue of
Sentence (2) or (3), the principal ventilation fan shall be controlled by a manual switch located in the kitchen or bathroom
and wired in parallel with the manual switch required by Sentence 9.32.3.3.(5).
(8) Where a supplemental exhaust fan required by this Article is controlled by a dehumidistat or other automatic control
in addition to the manual switch required by Sentence (6), the manual switch shall be capable of activating the fan
regardless of the setting of the automatic control.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
← Previous9.32.3.6. Exhaust-Only Ventilation Systems (See Note A-9.3Next →9.32.3.8. Protection Against Depressurization (See Note A-
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.