PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.32.3.6.Exhaust-Only Ventilation Systems (See Note A-9.32.3.6.)
(1) A ventilation system with no provision for the introduction of outdoor air to the dwelling unit may only be used
where the dwelling unit
(a) contains no solid-fuel-burning appliance, no fireplace of other than direct-vented type, and no other fuel-fired
space- or water-heating appliance of other than direct-vented or mechanically vented types, and
(b) has a forced air distribution system with a circulation fan with a rated capacity equal to at least 5 times the actual
normal operating exhaust capacity of the fan installed to satisfy the requirement for a principal ventilation fan, a
supply side that complies with Sentences 9.32.3.5.(10) to (12), and a return side that complies with Articles
9.33.6.12. and 9.33.6.13.
(2) Except as provided in Sentence (3), where an exhaust-only system is installed, the principal ventilation fan control
required by Sentence 9.32.3.3.(5) shall be wired in such a way that, where applicable, activation of the principal
ventilation fan automatically activates the circulation fan of the forced air distribution system required by Clause (1)(b) at
its rated capacity.
(3) Interlocking the forced air distribution system's circulation fan with the principal ventilation fan as required by
Sentence (2) is not required where the forced air distribution system is equipped with a control that automatically
activates the circulation fan at user-selected intervals.
← Previous9.32.3.5. Ventilation Systems Not Used in Conjunction withNext →9.32.3.7. Supplemental Exhaust (See Note A-9.32.3.7.)
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.