Can an exit pass through a lobby under the Ontario Building Code?
Yes, but only one required exit may lead through a lobby, the lobby floor must be close to grade, travel through the lobby is limited to about 15 m, and the lobby must be separated and finished to restrict fire and combustible content.
Paraphrased for clarity — open this provision in the BUILDAiD Library for the exact wording.
This allowance is what lets one stair in a typical tower discharge through the ground-floor lobby instead of directly outdoors, saving valuable street frontage. The second stair must still exit directly outside or through an exit passageway. Watch lobby programming: cafes, retail kiosks and furniture groupings can conflict with the hazard restriction, and mail rooms or property management offices opening into the lobby need review. Measure the 15 m across the actual path to the door.
One of the building's exit stairs is allowed to empty into the main ground-floor lobby, as long as the front door is a short walk away and the lobby is kept safe. The other stair must lead outside more directly.