PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.4.4.2.Exits Through Lobbies
(1) Except as permitted by Sentence (2), no exit from a floor area above or below the first storey shall lead through a
lobby.
(2) Not more than one exit from a floor area is permitted to lead through a lobby, provided
(a) the lobby floor is not more than 4.5 m above grade,
(b) the path of travel through the lobby to the outdoors is not more than 15 m,
(c) the adjacent rooms or premises having direct access to the lobby do not contain a residential occupancy or an
industrial occupancy, except that dwelling units may open directly onto the lobby, where
(i) from the interior of the exit stair that opens onto the lobby there is alternate means of egress not leading
through the lobby and such means of egress is entirely within the same storey as the lobby, or
(ii) the floor area is sprinklered,
(d) except as required by Clause (g), the lobby is not located within an interconnected floor space other than as
described in Sentence 3.2.8.2.(6),
(e) the lobby conforms to the requirements for exits, except that
(i) rooms other than service rooms and storage rooms are permitted to open onto the lobby,
(ii) the fire separation between the lobby and a room used for the sole purpose of control and supervision of the
building need not have a fire-resistance rating,
(iii) the fire separation between the lobby and adjacent occupancies that are permitted to open onto the lobby need
not have a fire-resistance rating provided the lobby and adjacent occupancies are sprinklered, and
(iv) passenger elevator entrances are permitted to open onto the lobby provided the elevator entrance doors are
designed to remain closed except while loading and unloading,
(See Note A-3.4.4.2.(2)(e))
(f) a fire separation, constructed in accordance with Sentence 3.4.4.1.(1), is maintained between the lobby and any exit
permitted by this Sentence to lead through the lobby, and
(g) that if the exit serves a hotel, the lobby is not located within an interconnected floor space.
← Previous3.4.4.1. Fire-Resistance Rating of Exit SeparationsNext →3.4.4.3. Exterior Passageway Exceptions
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.