How do you build a wall or floor that meets STC 50 in Ontario?
Use a tested assembly, typically double or staggered studs, or resilient channels on one side, with absorptive insulation in the cavity and often double layers of gypsum board, selected from OBC Supplementary Standard SB-3 or manufacturer test reports.
Paraphrased for clarity — open this provision in the BUILDAiD Library for the exact wording.
The classic STC 50+ recipes are: wood studs with resilient channel on one side, cavity insulation, and 5/8-inch Type X drywall (double-layered on at least one side), or a double-stud wall for higher performance. Execution kills ratings more than design: screws hitting studs through resilient channel, back-to-back electrical boxes, unsealed perimeter gaps, and pot lights all short-circuit the assembly. Seal edges with acoustical sealant and offset penetrations. For floors above basement apartments, add insulation, resilient channel, and double drywall to the ceiling below.
You reach STC 50 with proven recipes: insulation in the wall or ceiling cavity, springy metal channels so drywall isn't rigidly attached, and extra drywall layers. Sloppy details like gaps or back-to-back outlets ruin an otherwise good wall.