OBC DIVISION B · PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code

Section 9.18 — Crawl Spaces

Full text of Section 9.18 (Crawl Spaces) — Division B, Part 9 (Housing and Small Buildings) of the 2024 Ontario Building Code, with every article reproduced below.

9.18.1.General

9.18.1.1.Application permalink →

(1) In this Section, a crawl space refers to an enclosed space between the underside of a floor assembly and the ground cover directly below, with a clearance less than 1 800 mm in height.

9.18.1.2.Foundations permalink →

(1) Foundations enclosing crawl spaces shall conform to Section 9.15.

9.18.1.3.Heated and Unheated Crawl Spaces permalink →

(1) Crawl spaces shall be considered to be heated where the space (a) is used as a warm air plenum, (b) contains heating ducts or heating pipes that are not sealed and insulated to minimize heat loss to the space, or (c) is not separated from heated space in accordance with Section 9.25. (2) Heating of heated crawl spaces shall conform to Section 9.33. (3) Insulation, an air barrier system and a vapour barrier shall be installed in the walls of heated crawl spaces in accordance with Section 9.25.

9.18.2.Access

9.18.2.1.Access Openings permalink →

(1) An access opening of not less than 500 mm by 700 mm shall be provided to each crawl space where the crawl space serves a single dwelling unit, and not less than 550 mm by 900 mm for other crawl spaces. (2) Access openings shall be fitted with a door or hatch, except when the crawl space is heated and the access opening into the crawl space is from an adjacent heated space.

9.18.3.Ventilation

9.18.3.1.Ventilation of Unheated Crawl Spaces permalink →

(1) Unheated crawl spaces shall be ventilated by natural or mechanical means. (2) Where an unheated crawl space is ventilated by natural means, ventilation shall be provided to the outside air by not less than 0.1 m² of unobstructed vent area for every 50 m² of floor area. (3) Vents shall be (a) uniformly distributed on opposite sides of the building, and (b) designed to prevent the entry of snow, rain and insects.

9.18.3.2.Ventilation of Heated Crawl Spaces permalink →

(1) Heated crawl spaces shall be ventilated in accordance with Section 9.32.

9.18.4.Clearance (See also Article 9.3.2.9.)

9.18.4.1.Access Way to Services permalink →

(1) Where equipment requiring service such as plumbing cleanouts, traps and burners is located in crawl spaces, an access way with a height and width of not less than 600 mm shall be provided from the access door to the equipment and for a distance of 900 mm on the side or sides of the equipment to be serviced.

9.18.5.Drainage

9.18.5.1.Drainage permalink →

(1) Except where it can be shown to be unnecessary, the ingress of water into a crawl space shall be controlled by grading or drainage. (2) Drainage of foundation walls shall conform to Article 9.14.2.1. (3) Drainage of the ground cover or floor-on-ground in the crawl space shall conform to Subsection 9.16.3. (4) Drains shall conform to Section 9.14.

9.18.6.Ground Cover

9.18.6.1.Ground Cover in Unheated Crawl Spaces permalink →

(1) Where a crawl space is unheated, a ground cover shall be provided consisting of not less than (a) 50 mm of asphalt, (b) 100 mm of 15 MPa Portland cement concrete, (c) Type S roll roofing, or (d) 0.10 mm polyethylene. (2) Joints in sheet-type ground cover required in Sentence (1) shall be lapped not less than 100 mm and weighted down.

9.18.6.2.Ground Cover in Heated Crawl Spaces permalink →

(1) Where a crawl space is heated, a ground cover consisting of not less than 0.15 mm polyethylene sheet conforming to CAN/CGSB-51.34-M, “Vapour Barrier, Polyethylene Sheet, for Use in Building Construction,” shall be installed as part of an air barrier system in accordance with Subsection 9.25.3. (2) The ground cover required in Sentence (1) shall have its joints lapped not less than 300 mm, and (a) be sealed and evenly weighted down, or (b) be covered with concrete not less than 50 mm thick. (3) The perimeter of the ground cover required in Sentence (1) shall be sealed to the foundation wall. (See Notes A- 9.13.4., A-9.25.3.4. and 9.25.3.6., and A-9.25.3.6.(2) and (3)) (4) All penetrations of the ground cover required in Sentence (1) shall be sealed against air leakage. (See Subsection 9.25.3.)

9.18.7.Fire Protection

9.18.7.1.Crawl Spaces as Warm Air Plenums permalink →

(1) Only crawl spaces under 1-storey portions of dwelling units shall be used as warm air plenums. (2) Enclosing material in crawl spaces described in Sentence (1), including insulation, shall have a surface flame-spread rating not greater than 150. (3) Combustible ground cover used as enclosing material in Sentence (2) shall be covered with noncombustible material. (See Note A-9.18.7.1.(3) and (4)) (4) Noncombustible material described in Sentence (3) shall (a) extend not less than 300 mm beyond the projection of a register opening, and (b) have turned-up edges. (See Note A-9.18.7.1.(3) and (4))

Understand any provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.