PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.18.3.1.Ventilation of Unheated Crawl Spaces
(1) Unheated crawl spaces shall be ventilated by natural or mechanical means.
(2) Where an unheated crawl space is ventilated by natural means, ventilation shall be provided to the outside air by not
less than 0.1 m² of unobstructed vent area for every 50 m² of floor area.
(3) Vents shall be
(a) uniformly distributed on opposite sides of the building, and
(b) designed to prevent the entry of snow, rain and insects.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.