PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.32.3.12.Heat Recovery Ventilators (See Note A-9.32.3.12.)
(1) This Article shall apply to heat recovery ventilators installed to provide one or more of the fans required by this
Subsection.
(2) Two or more heat recovery ventilators shall not be connected in parallel airflow to a common air supply duct, unless
specifically permitted by the manufacturer.
(3) Two or more heat recovery ventilators shall not be connected in parallel airflow to a common downstream exhaust
duct.
(4) All start-up procedures recommended by the manufacturer, including air balancing and airflow determination, shall
be followed.
(5) A means for the free flow of condensate shall be provided in accordance with the manufacturer's recommendations
or, in their absence, a condensate drain of at least 1/2 inch nominal pipe size pitched in the direction of flow and complete
with a trap or condensate pump of sufficient capacity shall be installed and connected to the dwelling unit's drain, waste
and vent system.
(6) The heat recovery ventilator and all condensate lines shall be installed in a space where the ambient temperature will
not adversely affect the operation of the system.
← Previous9.32.3.11. Ducts (See Note A-9.32.3.11.)Next →9.32.3.13. Outdoor Intake and Exhaust Openings
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.