9.10.18.5.Smoke Detectors in Recirculating Air Handling Systems
(1) Except for a recirculating air system serving not more than one dwelling unit, where a fire alarm system is required
to be installed, every recirculating air handling system shall be designed to prevent the circulation of smoke upon a signal
from a duct-type smoke detector where such system supplies more than one suite on the same floor or serves more than
1 storey.
← Previous9.10.18.4. Rooms and Spaces Requiring Heat Detectors or SmoNext →9.10.18.6. Portions of Buildings Considered as Separate Bui
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.