9.10.18.4.Rooms and Spaces Requiring Heat Detectors or Smoke Detectors
(1) Where a fire alarm system is required, every public corridor in buildings of residential occupancy and every exit
stair shaft shall be provided with smoke detectors.
(2) Except as provided in Sentence (3), if a fire alarm system is required in a building that is not sprinklered, fire
detectors shall be installed in the following spaces:
(a) storage rooms not within dwelling units,
(b) service rooms not within dwelling units,
(c) janitors’ rooms,
(d) rooms in which hazardous substances are to be used or stored, (See Note A-3.3.1.2.(1))
(e) elevator hoistways, chutes and dumbwaiter shafts, and
(f) laundry rooms in buildings of residential occupancy, except those within dwelling units.
(3) Except as required in Sentence (4), heat detectors and smoke detectors described in Sentence (2), are not required in
dwelling units or in sprinklered buildings in which the sprinkler system is electrically supervised and equipped with a
water flow alarm.
(4) Where a fire alarm system is required in a hotel, heat detectors shall be installed in every room in a suite and in
every room not located in a suite in a floor area containing a hotel, other than washrooms within a suite, saunas,
refrigerated areas and swimming pools.
← Previous9.10.18.3. Design and Installation RequirementsNext →9.10.18.5. Smoke Detectors in Recirculating Air Handling Sy
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.