9.10.18.6.Portions of Buildings Considered as Separate Buildings
(1) Except as provided in Sentence (2), where a vertical fire separation having a fire-resistance rating of at least 1 h
separates a portion of a building from the remainder of the building and there are no openings through the fire separation
other than those for piping, tubing, wiring and conduit, the requirements for fire alarm and detection systems may be
applied to each portion so separated as if it were a separate building.
(2) The permission in Sentence (1) to consider separated portions of a building as separate buildings does not apply to
service rooms and storage rooms.
← Previous9.10.18.5. Smoke Detectors in Recirculating Air Handling SyNext →9.10.18.7. Central Vacuum Systems
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.