3.5.3.3.Fire Separations for Elevator Machine Rooms
(1) Except as permitted by Sentence (2), a room containing elevator machinery shall be separated from all other parts of
the building by a fire separation having a fire-resistance rating not less than that required for the vertical service space
containing the elevator hoistway.
(2) A room containing elevator machinery need not be separated from the elevator hoistway that it serves provided the
room and the hoistway are separated from all other parts of the building by a fire separation having a fire-resistance
rating not less than that required for the vertical service space containing the elevator hoistway.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.