3.5.3.2.Vertical Service Spaces for Dumbwaiters
(1) A vertical service space containing a dumbwaiter shall be separated from all other portions of each adjacent storey
by a fire separation having a fire-resistance rating conforming to Table 3.5.3.1. for the fire-resistance rating required by
Subsection 3.2.2. for
(a) the floor assembly above the storey, or
(b) the floor assembly below the storey, if there is no floor assembly above.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
← Previous3.5.3.1. Fire Separations for Elevator HoistwaysNext →3.5.3.3. Fire Separations for Elevator Machine Rooms
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.