3.5.4.1.Elevator Car Dimensions
(1) Except as provided in Sentence (2), if an elevator is installed to conform to the requirements of Article 3.3.1.7., or if
one or more elevators are provided in a building more than three storeys in building height, each storey having elevator
service shall be served by at least one elevator that has inside dimensions that will accommodate and provide adequate
access for a patient stretcher 2 010 mm long and 610 mm wide in the prone position. (See Note A-3.5.4.1.(1))
(2) The inside dimensions stipulated in Sentence (1) do not apply to limited-use/limited-application elevators designed
and installed in accordance with ASME A17.1 / CSA B44, “Safety Code for Elevators and Escalators.”
(3) An elevator satisfying the requirements of Sentence (1) shall be clearly identified on the main entrance level of the
building.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.