PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.4.6.16.Door Release Hardware
(1) Except for dwelling units, except for devices on doors serving a contained use area or an impeded egress zone
designed to be released in conformance with Article 3.3.1.13., and except as permitted by Sentence (5), locking, latching
and other fastening devices on every exit door shall permit the door to be readily opened from the inside with not more
than one releasing operation and without requiring keys, special devices or specialized knowledge of the door opening
mechanism. (See Note A-3.4.6.16.(1))
(2) If a door is equipped with a latching mechanism, a device complying with Sentence (3) shall be installed on
(a) every exit door from a floor area containing an assembly occupancy having an occupant load more than 100,
(b) every door leading to an exit lobby from an exit stair shaft, and every exterior door leading from an exit stair shaft in
a building having an occupant load more than 100, and
(c) every exit door from a floor area containing a high-hazard industrial occupancy.
(3) The device required in Sentence (2) shall
(a) extend across not less than one-half of the width of the door,
(b) release the latch, and
(c) allow the door to swing wide open when a force not more than that specified in Sentence 3.8.3.3.(7) is applied to the
device in the direction of travel to the exit.
(4) Except as required by Sentence 3.8.3.3.(7), every exit door shall be designed and installed so that, when the latch is
released, the door will open under a force of not more than 90 N, applied at the knob or other latch releasing device.
(5) Except as permitted by Sentence 3.3.1.13.(6), electromagnetic locks that do not incorporate latches, pins or other
similar devices to keep the door in the closed position are permitted to be installed on exit doors other than doors
described in Sentence (6) provided
(a) the building is equipped with a fire alarm system conforming to Subsection 3.2.4.,
(b) the locking device, and all similar devices in the access to exit leading to the exit door, are installed as ancillary
devices to the fire alarm system and release immediately upon activation of
(i) the alarm signal where a single-stage fire alarm system is installed,
(ii) except as provided in Subclause (iii), the alert signal where a 2-stage fire alarm system is installed, or
(iii) the alarm signal of a 2-stage fire alarm system installed in a care, care and treatment or detention occupancy
or in a retirement home,
(c) the locking device releases immediately upon loss of power controlling the electromagnetic locking mechanism and
its associated auxiliary controls,
(d) the locking device releases immediately upon actuation of a manually operated switch readily accessible only to
authorized personnel and located near the main entrance of the building or in the central alarm and control facility of
Sentence 3.2.6.7.(1),
(e) the locking device releases immediately upon a fault being detected in the electrical circuit between the fire alarm
control panel and the controller of the locking device,
(f) the locking device releases immediately upon the operation of a manual station for the fire alarm system located on
the wall not more than 600 mm from the door,
(g) a visual information sign complying with Article 3.8.3.1. that displays the words EMERGENCY EXIT
UNLOCKED BY FIRE ALARM is permanently mounted on the door,
(h) a tactile information sign complying with Article 3.8.3.1. that displays the words EMERGENCY EXIT
UNLOCKED BY FIRE ALARM is permanently mounted near the door,
(i) upon release, the locking device must be reset manually by the actuation of the switch referred to in Clause (d),
(j) the operation of any by-pass switch, where provided for testing of the fire alarm system, causes an audible signal
and a visual signal to be indicated at the fire alarm annunciator panel and at the monitoring station referred to in
Sentence 3.2.4.8.(4),
(k) emergency lighting conforming to 3.2.7.3.(1) is provided, and
(l) where they are installed on doors providing emergency crossover access to floor areas from exit stairs in accordance
with Article 3.4.6.18.,
(i) the locking device releases immediately upon the operation of a manual station for the fire alarm system
located on the wall on the exit stair side not more than 600 mm from the door,
(ii) a visual information sign displaying the words RE-ENTRY DOOR UNLOCKED BY FIRE ALARM that
complies with Article 3.8.3.1. is permanently mounted on the door on the exit stair side, and
(iii) a tactile information sign displaying the words RE-ENTRY DOOR UNLOCKED BY FIRE ALARM that
complies with Article 3.8.3.1. is permanently mounted near the door on the exit stair side.
(See Note A-3.4.6.16.(5))
(6) Reserved.
(7) Door release hardware for the operation of the doors referred to in this Section shall be installed between 900 mm
and 1 100 mm above the finished floor.
(8) Except as permitted by Sentences (9) and (10), electromagnetic locks are not permitted to be installed on exit doors
(a) described in Clause (2)(a), (b) or (c),
(b) serving an elementary or secondary school, or
(c) leading directly from a high-hazard industrial occupancy.
(9) Electromagnetic locks are permitted to be installed on an exterior door leading from an exit stairway in a building
containing only a Group B, Division 2 major occupancy, a Group B, Division 3 major occupancy or a retirement home.
(10) Electromagnetic locks are permitted to be installed on an exit door that serves only a gaming premises if
(a) the gaming premises is located within a sprinklered floor area,
(b) smoke detectors are installed in each room and each corridor accessible to the public,
(c) a force of not more than 90 N applied to the door opening hardware initiates an irreversible process that will release
the locking device within 15 s and not relock until the door has been opened, and
(d) a legible sign conforming with Clauses (5)(g) and(h) is permanently mounted on the exit door to indicate that the
locking device will release within 15 s of applying pressure to the door release hardware.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.