PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code

3.4.6.12.Direction of Door Swing

(1) Except for doors serving a single dwelling unit and except as permitted by Sentences (2) and (3) and Article 3.4.6.14., every exit door shall (a) open in the direction of exit travel, and (b) swing on its vertical axis. (2) Except in a high-hazard industrial occupancy, an exit door need not swing in the direction of exit travel where it serves (a) a room, suite or floor area having an occupant load of not more than 60 persons, or (b) as part of a means of egress from more than one floor area and the floor areas so served have a total occupant load of not more than 60 persons. (3) Exit doors need not conform to Sentence (1) where they serve (a) storage garages serving not more than one dwelling unit, (b) accessory buildings serving not more than one dwelling unit, or (c) storage suites not more than 28 m2 in area that are on the first storey of a warehouse and open directly outdoors at ground level.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.