3.4.6.11.Doors (See also Sentence 3.8.3.6.(17))
(1) The distance between a stair riser and the leading edge of a door during its swing shall be not less than 300 mm.
(2) Except as provided in Sentence (3) and where a threshold is used to contain spillage, a threshold for a doorway in an
exit shall be not more than 13 mm higher than the surrounding finished floor surface.
(3) No exit door shall open directly onto a step except that, if there is danger of blockage from ice or snow, an exit door
is permitted to open onto not more than one step which shall be not more than 150 mm high.
(4) Exit doors shall be clearly identifiable. (See Note A-3.4.6.11.(4))
(5) No door leaf in an exit doorway with more than one leaf shall be less than 610 mm wide.
(6) Where an exit door leading directly to the outside is subject to being obstructed by parked vehicles or storage
because of its location, a visible sign or a physical barrier prohibiting such obstructions shall be installed on the exterior
side of the door.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.