PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code

3.4.3.4.Headroom Clearance (See Note 3.4.3.4.)

(1) Except as provided by Sentences (2), (4) and (5), every exit shall have a clear height over the clear width of the exit of not less than 2 100 mm. (2) The clear height of stairways shall be measured vertically, over the clear width of the stairway, from a straight line tangent to the tread and landing nosings to the lowest point above, and shall not be less than 2 050 mm. (See Note A- 9.8.7.4.) (3) The clear height of landings shall be measured within the clear width of the landing vertically to the lowest element above. (4) Except as permitted by Sentence (5), the clear height of doorways shall not be less than 2 030 mm. (5) No door closer or other device shall be installed so as to reduce the clear height of a doorway to less than 1 980 mm.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.