3.4.3.3.Exit Width Reduction
(1) Except as permitted by Sentences (2) to (4), no fixture, turnstile or construction shall project into or be fixed within
the required width of an exit.
(2) Swinging doors in their swing shall not reduce the required width of exit stairs or landings to less than 750 mm or
reduce the width of an exit passageway to less than the minimum required width.
(3) Exit doors shall be installed so that, when open, they shall neither diminish nor obstruct the required width of the
exit by more than 50 mm for each door leaf.
(4) Handrails and construction below handrails, including handrail supports and stair stringers, are permitted to project
into the required width of means of egress but the projections shall be not more than 100 mm on each side of the required
width.
(5) In an elementary or secondary school, where a stair lift is installed in an exit stair, an intermediate handrail shall be
installed between the path of travel of the stair lift and the remainder of the stair to ensure that the stair lift will not reduce
the required width of the exit stair.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.