3.2.2.9.Crawl Spaces
(1) For the purposes of Articles 3.1.11.6., 3.2.1.4. and 3.2.1.5., a crawl space shall be considered as a basement if it is
(a) more than 1.8 m high between the lowest part of the floor assembly and the ground or other surface below,
(b) used for any occupancy,
(c) used for the passage of flue pipes, or
(d) used as a plenum in combustible construction.
(2) A floor assembly immediately above a crawl space is not required to be constructed as a fire separation and is not
required to have a fire-resistance rating provided the crawl space is not required to be considered as a basement by
Sentence (1).
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.