PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.1.9.1.Firestops
(1) Except as provided in Sentences (2) to (7) and Article 3.1.9.3., penetrations of a fire separation or a membrane
forming part of an assembly required to have a fire-resistance rating shall be
(a) sealed by a firestop that, when subjected to the fire test method in CAN/ULC-S115, “Standard Method of Fire Tests
of Firestop Systems,” has an F rating not less than the required fire-resistance rating of the fire separation, or
(b) cast-in-place, where the item penetrating the fire separation is steel, ferrous, copper, concrete or masonry. (See Note
A-3.1.9.1.(1)(b))
(See also Article 3.1.9.4. for requirements regarding penetrations by combustible drain, waste and vent piping.)
(2) Except as permitted in Sentence (6), penetrations of a firewall or a horizontal fire separation that is required to have
a fire-resistance rating in conformance with Article 3.2.1.2. shall be sealed at the penetration by a firestop that, when
subjected to the fire test method in CAN/ULC-S115, “Standard Method of Fire Tests of Firestop Systems,” has an FT
rating not less than the fire-resistance rating for the fire separation.
(3) Except as permitted in Sentences (6) and (7), penetrations of a fire separation in conformance with Sentence
3.6.4.2.(2) shall be sealed by a firestop that, when subjected to the fire test method in CAN/ULC-S115, “Standard Method
of Fire Tests of Firestop Systems,” has an FT rating not less than the fire-resistance rating for the fire separation of the
assembly.
(4) Sprinklers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a
fire-resistance rating without having to meet the firestop requirements of Sentences (1) to (3), provided the annular space
created by the penetration of a fire sprinkler is covered by a metal escutcheon plate in accordance with NFPA 13,
“Standard for the Installation of Sprinkler Systems.”
(5) Unless specifically designed with a firestop, fire dampers are permitted to penetrate a fire separation or a membrane
forming part of an assembly required to have a fire-resistance rating without having to meet the firestop requirements of
Sentences (1) to (3), provided the fire damper is installed in conformance with NFPA 80, “Standard for Fire Doors and
Other Opening Protectives.”
(6) Service equipment penetrations through a horizontal fire separation having a fire-resistance rating as described in
Sentences (2) and (3) that are contained within the cavity of a wall above and below the horizontal fire separation are
permitted to be sealed at the penetration by a firestop that, when subjected to the fire test method in CAN/ULC-S115,
“Standard Method of Fire Tests of Firestop Systems,” has an F rating not less than the fire-resistance rating for the fire
separation.
(7) Service equipment penetrations through a horizontal fire separation having a fire-resistance rating as described in
Sentence (3) are permitted to be sealed at the penetration by a firestop that, when subjected to the fire test method in
CAN/ULC-S115, “Standard Method of Fire Tests of Firestop Systems,” has an F rating not less than the fire-resistance
rating for the fire separation, provided the penetration
(a) is contained within the concealed space of a floor or ceiling assembly having a fire-resistance rating,
(b) is located above a ceiling membrane that is a horizontal fire separation, or
(c) is contained within a horizontal service space conforming to Subsection 3.6.4. that is directly above or below the
floor.
← Previous3.1.8.20. Sprinkler Protected Glazed Wall AssemblyNext →3.1.9.2. Service Equipment Penetrations
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.