3.1.8.20.Sprinkler Protected Glazed Wall Assembly
(1) A sprinkler protected glazed wall assembly shall be constructed in accordance with the requirements of CAN/ULC-
S136, “Standard Method of Fire Test of Sprinkler Protected Window Systems.”
(2) A sprinkler protected glazed wall assembly shall not be installed in
(a) fire separations requiring a fire-resistance rating of more than 2 h,
(b) a firewall,
(c) a high-hazard industrial occupancy, or
(d) any part of an exit serving
(i) a floor area subject to the requirements of Subsection 3.2.6.,
(ii) a care occupancy,
(iii) a care and treatment occupancy,
(iv) a detention occupancy, or
(v) a residential occupancy.
(3) Where a sprinkler protected glazed wall assembly is installed in an exit fire separation permitted in Sentence (2),
(a) the building shall be sprinklered throughout, and
(b) the exits protected with the sprinkler protected glazed wall assemblies shall not comprise more than one-half of the
required number of exits from any floor area.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.