3.1.9.2.Service Equipment Penetrations
(1) Ducts, electrical outlet boxes, pipes, totally enclosed raceways, optical fibre cables, electrical wires and cables, and
other similar service equipment are permitted to penetrate a fire separation or a membrane forming part of an assembly
required to have a fire-resistance rating, provided they are protected at the penetration with a firestop conforming to
Sentence 3.1.9.1.(1). (See Note A-3.1.9.2.(1))
(2) Combustible totally enclosed raceways that are embedded in a concrete floor slab are permitted in an assembly
required to have a fire-resistance rating, provided the concrete cover between the raceway and the bottom of the slab is
not less than 50 mm.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.