PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.1.13.7.High Buildings
(1) Except as permitted by Sentences (2) to (4), the interior wall, ceiling and floor finishes in a building regulated by the
provisions of Subsection 3.2.6. shall conform to the flame-spread rating requirements in Articles 3.1.13.2. to 3.1.13.6.
and 3.1.13.11. and to the flame-spread rating and smoke developed classification values in Table 3.1.13.7.
(2) Except for a building of Group B major occupancy and elevator cars, the flame-spread rating and smoke developed
classification of interior wall, floor and ceiling finishes need not conform to the values in Table 3.1.13.7., provided the
building is sprinklered.
(3) Trim and millwork in an exit stairway, a vestibule to an exit stairway, a lobby described in Sentence 3.4.4.2.(2), or a
corridor not within a suite need not conform to the flame-spread rating and smoke developed classification requirements
of Sentence (1), provided they have
(a) a flame-spread rating not more than 150,
(b) a smoke developed classification not more than 300, and
(c) an aggregate area not more than 10% of the area of the wall or ceiling on which they occur.
Table 3.1.13.7.
Flame-Spread Rating and Smoke Developed Classification in High Buildings
Forming Part of Sentences 3.1.13.7.(1) and (2)
Maximum Smoke Developed
Maximum Flame-Spread Rating
Classification
Location or Element
Wall Ceiling Floor Wall Ceiling Floor
Surface Surface(1) Surface Surface Surface(1) Surface
Exit stairways, vestibules to exit stairs and lobbies
25 25 25 50 50 50
described in Sentence 3.4.4.2.(2)
Corridors not within suites (2) (2) 300 100 50 500
Elevator cars 75 75 300 450 450 450
Elevator vestibules 25 25 300 100 100 300
Service spaces and service rooms 25 25 25 50 50 50
Other locations and elements (2) (2) No limit 300 50 No limit
Notes to Table 3.1.13.7.:
(1) See Sentence 3.1.13.4.(1) for lighting elements.
(2) Other requirements of this Part apply.
(4) A door serving an exit stairway, a vestibule to an exit stairway, a lobby described in Sentence 3.4.4.2.(2), or a corridor
not within a suite need not conform to the flame-spread rating and smoke developed classification requirements of
Sentence (1) provided
(a) it has a flame-spread rating not more than 200,
(b) it has a smoke developed classification not more than 300, and
(c) the aggregate area of all doors is not more than 10% of the area of the wall in which they are located.
(5) Except as permitted in Sentences (6) to (8), plumbing fixtures in a building regulated by the provisions of Subsection
3.2.6. shall have a smoke developed classification not more than 300.
(6) A plumbing fixture that is not located in a Group B occupancy need not comply with Sentence (5) if the building is
sprinklered throughout.
(7) A plumbing fixture may have a smoke developed classification more than 300 but not more than 500 if,
(a) it is in a room where the wall surfaces have a smoke developed classification not more than 200, and
(b) it is located in,
(i) a Group C occupancy, or
(ii) a Group B occupancy and the building is sprinklered throughout.
(8) A therapeutic bathing system in a Group B occupancy need not comply with Sentence (5) if the room in which it is
located,
(a) does not open directly into patients’ or residents’ sleeping rooms, and
(b) is sprinklered.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.