3.1.13.6.Corridors
(1) Except as permitted by Sentences (2) and (3), the flame-spread rating shall be not more than 75 for the interior wall
finish of
(a) a public corridor,
(b) a corridor used by the public in,
(i) an assembly occupancy, or
(ii) a care, care and treatment or detention occupancy,
(c) a corridor serving classrooms, or
(d) a corridor serving sleeping rooms in a care, care and treatment or detention occupancy.
(2) The flame-spread rating for corridors specified in Sentence (1) is permitted to be waived, provided the flame-spread
rating is not more than
(a) 25 on the upper half of the wall, and
(b) 150 on the lower half of the wall.
(3) Where the floor area is sprinklered throughout, the flame-spread ratings for corridors specified in Sentences (1) and
(2) shall be not more than 150.
(4) The flame-spread ratings specified in Sentences (1), (2) and (3) apply to occupancies in the corridor as well as to the
corridor itself.
(5) Except as provided in Sentence (6), the interior ceiling finish of corridors and occupancies referred to in Sentences
(1) and (4) shall have a flame-spread rating not more than 25.
(6) Where the floor area is sprinklered throughout, the flame-spread rating of the interior ceiling finish of corridors and
occupancies referred to in Sentences (1) and (4) shall be not more than 150.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.