3.1.13.8.Noncombustible Construction
(1) In a building required to be of noncombustible construction,
(a) the flame-spread ratings required by Subsection 3.1.5. shall apply in addition to the requirements in this Subsection,
and
(b) the flame-spread ratings for exits in this Subsection shall also apply to any surface in the exit that would be exposed
by cutting through the material in any direction, except that this requirement does not apply to doors, heavy timber
construction in a sprinklered building and fire-retardant-treated wood.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.